Mx480 router rack requirements, Rack size and strength – Juniper Networks MX480 User Manual

Page 78

Advertising
background image

Table 20: Site Preparation Checklist (continued)

Date

Performed By

For More Information

Item or Task

“MX480 Chassis Grounding
Specifications” on page 294

,

MX480 Router Grounding Cable Lug
Specifications,
MX480 Router Grounding Cable
Specifications

Locate sites for connection of system
grounding.

Measure distance between external power
sources and router installation site.

“Calculating Power Budget and
Power Margin for Fiber-Optic Cables”
on page 308

Calculate the optical power budget and optical
power margin.

Related

Documentation

MX480 Router Rack Requirements on page 54

MX480 Router Clearance Requirements for Airflow and Hardware Maintenance on
page 56

MX480 Router Cabinet Size and Clearance Requirements on page 57

MX480 Router Rack Requirements

The router can be installed in a rack. Many types of racks are acceptable, including
four-post (telco) racks and open-frame racks. An example of an open-frame rack appears
in

Figure 30 on page 55

.

Rack Size and Strength on page 54

Spacing of Mounting Bracket Holes on page 55

Connection to Building Structure on page 56

Rack Size and Strength

The router is designed for installation in a 19-in. rack as defined in Cabinets, Racks, Panels,
and Associated Equipment
(document number EIA-310-D) published by the Electronics
Industry Association (

http://www.eia.org

).

With the use of adapters or approved wing devices to narrow the opening between the
rails, the router fits into a 600-mm-wide rack or cabinet , as defined in the four-part
Equipment Engineering (EE); European telecommunications standard for equipment practice
(document number ETSI EN 300 119) published by the European Telecommunications
Standards Institute (

http://www.etsi.org

).

The rack rails must be spaced widely enough to accommodate the router chassis's
external dimensions: 14.0 in. (356 mm) high, 24.5 in. (622 mm) deep, and
17.45 in. (443 mm) wide. The spacing of rails and adjacent racks must also allow for the
clearances around the router and rack that are specified in

“MX480 Router Clearance

Requirements for Airflow and Hardware Maintenance” on page 56

.

Copyright © 2013, Juniper Networks, Inc.

54

MX480 3D Universal Edge Router Hardware Guide