Mx480 dc power specifications and requirements, Table 41: power supply electrical specifications – Juniper Networks MX480 User Manual

Page 325

Advertising
background image

WARNING:

The router is pluggable type A equipment installed in a

restricted-access location. It has a separate protective earthing terminal
(sized for UNC 1/4-20 ground lugs) provided on the chassis in addition to the
grounding pin of the power supply cord. This separate protective earthing
terminal must be permanently connected to earth.

CAUTION:

Power cords and cables must not block access to device

components or drape where people could trip on them.

Related

Documentation

Connecting Power to an AC-Powered MX480 Router with Normal-Capacity Power
Supplies on page 105

Replacing an MX480 AC Power Supply Cord on page 235

AC Electrical Specifications for the MX480 Router on page 297

Calculating Power Requirements for MX480 Routers on page 285

AC Power Circuit Breaker Requirements for the MX480 Router on page 298

MX480 DC Power Specifications and Requirements

DC Power Supply Electrical Specifications for the MX480 Router on page 301

DC Power Circuit Breaker Requirements for the MX480 Router on page 302

DC Power Source Cabling and Cable Specifications for the MX480 Router on page 303

DC Power Supply Electrical Specifications for the MX480 Router

Table 41 on page 301

lists the DC power supply electrical specifications.

Table 42 on

page 302

lists the DC power system specifications.

Table 41: Power Supply Electrical Specifications

Specification

Item

Normal-Capacity Power Supplies

1600 W

Maximum output power

33.3 A @ –48 V nominal operating voltage

DC input current rating

40 A

Maximum Input Current

Operating Range: –40.5 VDC to –72 VDC

Nominal: –48 VDC

DC input voltage