Warnings on refrigerant leakage, Check of concentration limit, Important – Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 115

Advertising
background image

WARNINGS ON REFRIGERANT LEAKAGE

For the amount of charge in this example:

The possible amount of leaked refrigerant gas in

rooms A, B and C is 10kg.

The possible amount of leaked refrigerant gas in

rooms D, E and F is 15kg.

NOTE 2 :

The standards for minimum room volume are as follows.
1) No partition (shaded portion)

2) When there is an effective opening with the adjacent

room for ventilation of leaking refrigerant gas (opening

without a door, or an opening 0.15% or larger than the

respective floor spaces at the top or bottom of the door).

3) If an indoor unit is installed in each partitioned room

and the refrigerant piping is interconnected, the

smallest room of course becomes the object.
But when a mechanical ventilation is installed

interlocked with a gas leakage detector in the smallest

room where the density limit is exceeded, the volume

of the next smallest room becomes the object.

NOTE 3 :

The minimum indoor floor area compared with the

amount of refrigerant is roughly as follows:

(When the ceiling is 2.7m high)

Check of Concentration Limit

The room in which the air conditioner is to be

installed requires a design that in the event of

refrigerant gas leaking out, its concentration will

not exceed a set limit.

The refrigerant R410A which is used in the air

conditioner is safe, without the toxicity or combustibility of

ammonia, and is not restricted by laws to be imposed

which protect the ozone layer. However, since it contains

more than air, it poses the risk of suffocation if its

concentration should rise excessively. Suffocation from

leakage of R410A is almost non-existent. With the recent

increase in the number of high concentration buildings,

however, the installation of multi air conditioner systems

is on the increase because of the need for effective use

of floor space, individual control, energy conservation by

curtailing heat and carrying power etc.

Most importantly, the multi air conditioner system is able

to replenish a large amount of refrigerant compared with

conventional individual air conditioners. If a single unit of

the multi conditioner system is to be installed in a small

room, select a suitable model and installation procedure

so that if the refrigerant accidentally leaks out, its

concentration does not reach the limit (and in the event

of an emergency, measures can be made before injury

can occur).

In a room where the concentration may exceed the limit,

create an opening with adjacent rooms, or install

mechanical ventilation combined with a gas leak

detection device.

The concentration is as given below.

Total amount of refrigerant (kg)

Min. volume of the indoor unit installed room (m³)

≤ Concentration limit (kg/m³)

The concentration limit of R410A which is used in multi

air conditioners is 0.3kg/m³.

NOTE 1 :

If there are 2 or more refrigerating systems in a single

refrigerating device, the amounts of refrigerant should be

as charged in each independent device.

Important

Outdoor unit

e.g.,
charged amount (15kg)

e.g., charged
amount (10kg)

Indoor unit

Room A Room B Room C Room D Room E Room F

Outdoor unit

Refrigerant piping

Indoor unit

Outdoor unit

Refrigerant piping

Indoor unit

Very

small

room

Small

room

Medium

room

Large room

Mechanical ventilation device - Gas leak detector

0

5

10

10

20

30

15

20

25

30

35

40

Range below the
density limit
of 0.3 kg/m³
(countermeasures
not needed)

Range above
the density limit
of 0.3 kg/m³
(countermeasures
needed)

Total amount of refrigerant

kg

Min.

indoor floor area

Advertising