53 – error mode detected by outdoor unit – Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 53

Advertising
background image

– 53 –

Error mode detected by outdoor unit

Check code

Indoor unit

4-Way

Under

High

Ceiling

Wall

F04

F04

F06

F06

F07

F12

F15

F08

F08

L29

F13

F31

L10

L29

P07

P15

P19

H01

H01

H02

H02

H03

H03

Cause of operation

Disconnection, short of discharge

temp. sensor (TD)

Disconnection, short of outdoor temp.

sensor (TE)

Disconnection, short of outdoor temp.

sensor (TL)

Disconnection, short of suction temp.

sensor (TS)

Miss-mounting of outdoor temp.

sensor (TE, TS)

Disconnection, short of outside temp.

sensor (TO)

Disconnection, short of heat sink

temp. sensor (TH)

Outdoor P.C. EEPROM error

Unset jumper of service P.C. board

Communication error between

outdoor P.C. board MCU

Heat sink overheat error
∗ Heat sink temp. sensor detected

over specified temperature.

Detection of gas leak
∗ Discharge temp. sensor (TD),

Suction temp. sensor (TS) detected

temperature over specified temp.

4-way valve inverse error
∗ After heating operation has started,

indoor heat exchanger temp. lowers

under the specified temp.

∗ After heating operation has started,

outdoor heat exchanger / suction

temp. rises over the specified temp.

Compressor break down
∗ Although operation has started,

operation frequency decreases and

operation stops.

Compressor lock
∗ Over-current detection after

compressor start-up

Current detection circuit error

Status of

air conditioner

Stop

Stop

Stop

Stop

Stop

Continue

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Condition

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Judgment and measures

1. Check discharge temp. sensor (TD).
2. Check outdoor P.C. board.

1. Check temp. sensor (TE).
2. Check outdoor P.C. board.

1. Check temp. sensor (TL).
2. Check outdoor P.C. board.

1. Check suction temp. sensor (TS).
2. Check outdoor P.C. board.

1. Check temp. sensor (TE, TS).
2. Check outdoor P.C. board.

1. Check outside temp. sensor (TO).
2. Check outdoor P.C. board.

1. Check outdoor P.C. board.

1. Check outdoor P.C. board.

1. Outdoor service P.C. board

Check model type setting jumper wire.

1. Check outdoor P.C. board.

1. Check screw tightening between PC. Board and heat

sink and check radiator grease.

2. Check heat sink blast path.

1. Check gas leak, recharge
2. Check full open of service valve.
3. Check PMV (Pulse Motor Valve).
4. Check broken pipe.
5. Check discharge temp. sensor (TD), suction temp.

sensor (TS).

1. Check operation of 4-way valve.
2. Check outdoor heat exchanger (TE), suction temp.

sensor (TS).

3. Check indoor heat exchanger sensor (TC).
4. Check 4-way valve coil.
5. Check PMV (Pulse Motor Valve).

1. Check power supply voltage. (AC187, 253V)
2. Overload operation of refrigerating cycle.
3. Wiring error of compressor (Open phase)

1. Trouble of compressor (Lock, etc.): Replace compressor.
2. Wiring error of compressor (Open phase)

1. Check outdoor P.C. board. (AC current detection circuit)

Operation of diagnostic function