Over-current protective control, High-pressure sw control, Current release value shift control – Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 42

Advertising
background image

– 42 –

8. Over-current protective control

1) When the over-current protective circuit detected an abnormal current, stop the compressor.
2) The compressor restarts after 2 minutes 30 seconds setting [1] as an error count.
3) When the error count [8] was found, determine an error and restart operation is not performed.
4) For the error display contents, confirm on the check code list.

9. High-pressure SW control

1) The operation frequency is controlled to restrain abnormal rising of high pressure by the High-pressure SW.
2) When cooling operation detects abnormal pressure of the stop zone, stop the compressor and the error

count becomes +1.

3) When the compressor stopped with 2), the compressor will restart only when the pressure lowers under

the reset pressure after 5 minutes.

STOP pressure

RESET pressure

601.8 + 0

⎛ 4.15 +0

.2 psi

– 29 psi ⎝

–0.2 MPa ⎠

464

± 29 psi (3.20 ± 0.2 MPa)

Pressure of High-pressure switch control

7. Current release value shift control

1) This control purposes to prevent troubles

of the electronic parts such as the

compressor driving elements and the

compressor during cooling operation.

2) The current release control value (11) is

selected from the following table

according to TO sensor value.

Current release control value (I1)

[A]

Temperature range

111.2°F (44°C) ≤ To

102.2°F (39°C) ≤ To < 111.2°F (44°C)

To < 102.2°F (39°C)

TO error

RAV-SP300AT2-UL

RAV-SP360AT2-UL

RAV-SP420AT2-UL

15.0
17.7
20.0
15.0

4) The error count when the compressor

stopped with 2) is cleared after the operation

continued for 10 minutes.
If the error count becomes [10] without clearing,

the error is determined and reactivation is not

performed.

5) For the error display contents, confirm on the

check code list.