Operation of diagnostic function

Check code

Indoor unit

4-Way

Under

High

Ceiling

Wall

P03

P03

P04

H04

P04

P05

P20

P22

P22

P26

P26

P29

P29

Cause of operation

Discharge temp. error
∗ Discharge temp. (TD) over

specified value was detected.

Case thermostat operation
∗ Abnormal overheat of compressor

High-pressure SW error

Power supply voltage error

High pressure protective operation
• During cooling operation, outdoor

temp. sensor (TL) detected

temperature over specified temp.

• During heating operation, indoor

temp. sensor (TC, TCJ) detected

temperature over specified temp.

Outdoor fan system error

Short-circuit error of compressor

driving element

Position detection circuit error

Status of

air conditioner

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Condition

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Judgment and measures

1. Check refrigerating cycle (Gas leak)
2. Trouble of electronic expansion valve
3. Check discharge temp. sensor (TD).

1. Check case thermostat and connector.
2. Check gas leak, recharge
3. Check full open of service valve.
4. Check PMV (Pulse Motor Valve).
5. Check broken pipe.

• Check full-open of service valve.
• Check outdoor fan error.
• Check outdoor fan motor error.
• Check clogging of outdoor PMV.
• Check loading of indoor/outdoor heat exchangers.
• Short-circuit of outdoor discharge/suction air
• Check outdoor P.C. board (I/F) error.
• Check error of fan system (air volume drop) at indoor side.
• Check miswiring of communication line between indoor and

outdoor.

• Check overcharge of refrigerant.

1. Check power supply voltage. AC198 to 253V

1. Check outdoor heat exchanger sensor (TL).
2. Check indoor heat exchanger sensor (TC, TCJ).
3. Check full open of service valve.
4. Check indoor/outdoor fan.
5. Check PMV (Pulse Motor Valve).
6. Check clogging and short circuit of indoor/outdoor heat

exchanger.

7. Overcharge of refrigerant. Recharge

1. Check lock of fan motor.
2. Check power supply voltage. AC198 to 253V
3. Check outdoor P.C. board.

1. When performing operation while taking-off compressor

wire, P26 error occurs. Check control P.C. board.

2. When performing operation while taking-off compressor

wire, an error does not occur. (Compressor rare short)

1. Check control P.C. board.