– 86 –

No.

†

Part name

Fan motor

Procedure

1) Perform works of Detachment 1 of



and

‚

.

2) Take off the flange nut fixing the fan motor and the propeller.

• Turning it clockwise, the flange nut can be loosened.

(To tighten the flange nut, turn counterclockwise.)

3) Remove the propeller fan.
4) Disconnect the connector for fan motor from the inverter.
5) Take off the fixing screws (2 pcs.) holding by hands so that

the fan motor does not fall.

NOTE:

Tighten the flange nut with torque 4.9Nm (50kgf/cm).

Remarks

Flange nut

Flange nut

Loosen the nut by

Loosen the nut by
turning clockwise

turning clockwise

Flange nut

Loosen the nut by
turning clockwise

Propeller fan

Propeller fan

Propeller fan

Fan motor

Fan motor

Fan motor

Partition plate

Partition plate

Partition plate

Compressor lead

Compressor lead

Case thermo

Case thermo

Compressor lead

Case thermo

Valve

Valve
support board

support board

Fusible plug

Fusible plug

Pressure

Pressure
switch

switch

Compressor bolt

Compressor bolt
(3 pcs.)

(3 pcs.)

Remove

Remove
(Suction pipe)

(Suction pipe)

Remove

Remove
(Discharge pipe)

(Discharge pipe)

Valve
support board

Fusible plug

Pressure
switch

Compressor bolt
(3 pcs.)

Remove
(Suction pipe)

Remove
(Discharge pipe)

1) Perform works of Detachment 1 of



,

‚

,

ƒ

and

„

.

2) Discharge refrigerant gas.
3) Remove the partition plate. (M4, 8 mm, 3 pcs.)
4) Remove the noise-insulator.
5) Remove the terminal covers of the compressor, and discon-

nect lead wires of the compressor and the compressor

thermo assembly from the terminal.

6) Remove pipes connected to the compressor with a burner.

CAUTION

Pay attention to that flame does not involve 4-way valve,

PMV, pressure SW, or fusible plug.

(If doing so, a malfunction may be caused.)

7) Remove the side cabinet (Left). (M4, 8 mm, 3 pcs.)
8) Take off the fixing screws of the bottom plate and heat

exchanger. (M4, 8 mm)

9) Take off the fixing screws of the valve clamping plate to the

bottom plate. (M4, 8 mm, 1 pc.)

10) Pull upward he refrigerating cycle.
11) Take off nut fixing the compressor to the bottom place.

CAUTION

When reconnecting the lead wires to the compressor

terminals after replacement of the compressor, be sure to

caulk the Faston terminal without loosening.

Compressor

‡