Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 71

Advertising
background image

– 71 –

Correct wiring.

Replace outdoor P.C. board.

Check outdoor P.C. board.

Defect

Replace

NO

NO

The same error does not occur in

operation without compressor lead.

Check compressor. (Rear short, etc.)

Defect

Replace

Is there no problem on connection

of compressor lead or reactor?

(Check referring to Wiring diagram.)

YES

YES

Check outdoor P.C. board.

Defect

Replace

Replace fan motor.

Check wiring construction.

Ask repair of power supply.

YES

NO

Is there no problem on power supply voltage?

208/230V ± 10V

Does the fan rotate without trouble when rotating

shaft of fan motor with hands during power-OFF?

Is there no problem on coil resistance of fan motor?

Between red and white lead wire

: 12 to 20

Ω

Between white and black lead wire : 12 to 20

Ω

Between black and red lead wire

: 12 to 20

Ω

YES

NO

CODE

No.

[P22]

[P26]

[P29]

No code

Outdoor

LED display

<Display 1> <Display 2>

¡

l

¡

¥

¡

¥

l

l

¡

¥

¡

¡

<Display 1> <Display 2>

¡

l

¡

¥

¡

l

l

¥

¡

¥

¡

¡

<Display 1> <Display 2>

¡

¥

¡

l

¡

¥

l

¥

¡

¥

¡

¡

<Display 1> <Display 2>

l

¥

¡

¥

¡

¥

l

¥

¡

¥

¡

¡

Check and troubleshooting

(Item without special mention Indicates part of outdoor unit.)

[Fan system error]

Single operation check for outdoor fan
1) Set SW804 of Dip switch as the following figure and then push SW801 for

approx. 1 second to check single operation of outdoor fan. Use this method to

check which fan, upper or lower fan, has a trouble.

• When pushing SW801 for 1 second

again or 2 minutes passed, the fan stops.

2) After check, turn off all Dip switch

SW804.

[Short-circuit of compressor drive element]

ON

12

3

4

SW804

SW801

Push

Outdoor fan single operation

[Position detection circuit error]

[Other error] Compressor disorder due to sudden change of load, etc.
∗ Although the display of outdoor LED outputs, the unit automatically restarts

and error is not determined.

∗ LED display also may output due to negative phase of compressor or wire

coming-off.