SW804

SW801

PMV coil

Spring

PMV main body

No.

‡

Part name

Compressor

Compressor lead

(Continued)

Procedure

3. Vacuuming

1) Connect the vacuum pump to the charge

port of the gas pipe valve and then drive

the vacuum pump.

2) Carry out vacuuming until the vacuum

low pressure gauge indicates 1 (mmHg).

NOTE:

Before vacuuming, open PMV fully. If PMV is

closed, vacuuming may be impossible between

the liquid pipe valve and PMV of the outdoor unit.

Forced full-opening method of PMV

∗ Turn on the leakage breaker.
∗ Turn on 1 and 3 of DIP SW804 on the control

P.C. board of the outdoor unit.

∗ Keep pushing SW801 on the control P.C. board

of the outdoor unit for 1 second or more.

∗ After pushing SW801 for 1 second or more,

turn off the leakage breaker within 2 minutes.

4. Refrigerant charging

1) Add the quantity of refrigerant specified

by the pipe length into the charge port of

the valve.

Remarks

1. Detachment

1) Perform work of Detachment



and

ƒ

.

2) While pulling the coil upward and

removing the spring which pinches the

copper pipe, remove the coil from PMV

main body.

2. Attachment

1) Match the spring to the copper pipe and

fix it.

PMV coil

ˆ