Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 43

Advertising
background image

– 43 –

4) The time of above d can be changed by

exchanging jumper [J805] and [J806] of the

outdoor control P.C. board.

(Setting at shipment: 150 minutes)

A zone

B zone

C zone
D zone

In normal To

In abnormal To

When status (TE0 – TE) – (To0 – To) ≥ 37.4°F (3°C)

When status (TE0 – TE) ≥ 37.4°F (3°C)

continued for 20 seconds

continued for 20 seconds

When status (TE0 – TE) – (To0 – To) ≥ 35.6°F (2°C)

When status (TE0 – TE) ≥ 35.6°F (2°C)

continued for 20 seconds

continued for 20 seconds

When status (TE ≤ –9.4°F (–23°C)) continued for 20 seconds

When compressor operation status of TE < 28.4°F (–2°C) is calculated by d portion

¡

: Short circuit,

×

: Open

10. Defrost control

1) In heating operation, defrost operation is performed when TE sensor satisfies any condition in A zone to

D zone.

2) During defrosting operation, it finishes if TE sensor continued 53.6°F (12°C) or higher for 3 seconds or

continued 44.6°F (7°C) ≤ TE < 53.6°F (12°C) for 1 minute.
The defrost operation also finishes when it continued for 10 minutes even if TE sensor temperature was

44.6°F (7°C) or lower.

3) After defrost operation was reset, the compressor stopped for approx. 40 seconds and then the heating

operation starts.

∗ The minimum TE value and To value between 10 and 15 minutes after heating operation has started

are stored in memory as TE0 and To0, respectively.

0

10

15

39

45

55

d

[min.]

TE ˚F (˚C)

28.4 (–2)

23.0 (–5)

14.0 (–10)

–9.4 (–23)

A zone

A zone

B zone

B zone

C zone

C zone

D zone

D zone

A zone

B zone

C zone

D zone

Start of heating operation

J805

¡
¡

Ч

Ч

d

150 minutes

Setting at shipment

90 minutes
60 minutes
30 minutes

J806

¡

Ч

¡

Ч

Advertising