3. Outdoor fan control

Revolution frequency allocation of fan taps [rpm]

3-1) Cooling fan control



The outdoor fan is controlled by TL sensor,

TO sensor and the operation frequency.

The outdoor fan is controlled by every 1

tap of DC fan control (SP240: 15 taps,

SP300, SP360, SP400: 14 taps).

‚

Only for 60 seconds after the operation

has started, the maximum fan tap

corresponding to the zone in the following

table is fixed and then the fan is controlled

by temperature of TL sensor.

WE tap

+1 tap / 20 sec

Up to the maximum

revolution frequency of each zone

Revolution frequency hold

–1 tap / 20 sec

Up to the minimum

revolution frequency of each zone

TL

˚F (˚C)

136.4 (58)

131.0 (55)

100.4 (38)

95.0 (35)

RAV-

SP300AT2-UL

SP360AT2-UL

SP420AT2-UL

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

Up

200

240

240

260

320

380

480

500

530

610

640

660

720

780

Down

200

280

360

400

500

520

550

630

660

700

740

820

RAV-

SP240AT2-UL

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

WF

200

230

260

300

340

380

420

460

520

570

600

630

670

710

740

∗ : WB for SP300

Temp. range

100.4°F (38°C) ≤ TO

84.2°F (29°C) ≤ TO < 100.4°F (38°C)

59°F (15°C) ≤ TO < 84.2°F (29°C)

41°F (5°C) ≤ TO < 59°F (15°C)

32°F (0°C) ≤ TO < 41°F (5°C)

24.8°F (–4°C) ≤ TO < 32°F (0°C)

TO < 24.8°F (–4°C)

TO error

20 Hz or lower

20Hz to 45Hz

45Hz or higher

Min.

Max.

Min.

Max.

Min.

Max.

W6

WC

W8

WE

WA

WE

W5

WB

W7

WD

W9

WD

W4

W8

W6

WA

W8

WC

W3

W6

W5

W8

W7

WA

W2

W4

W4

W6

W5

W8

W2

W3

W3

W5

W4

W6

OFF

OFF

OFF

W2

OFF

W3

OFF

WC

OFF

WE

OFF

WE

Temp. range

100.4°F (38°C) ≤ TO

84.2°F (29°C) ≤ TO < 100.4°F (38°C)

59°F (15°C) ≤ TO < 84.2°F (29°C)

41°F (5°C) ≤ TO < 59°F (15°C)

32°F (0°C) ≤ TO < 41°F (5°C)

24.8°F (–4°C) ≤ TO < 32°F (0°C)

TO < 24.8°F (–4°C)

TO error

20 Hz or lower

20Hz to 45Hz

45Hz or higher

Min.

Max.

Min.

Max.

Min.

Max.

W6

WC

W8

WC

WA

WE

W5

WB

W7

WC*

W9

WC

W4

W8

W6

WA

W8

WC

W3

W6

W5

W8

W7

WA

W2

W4

W4

W6

W5

W8

W2

W3

W3

W5

W4

W6

W1

W2

W1

W4

W2

W6

W1

WC

W1

WC

W2

WD

<RAV-SP240AT2-UL>

<RAV-SP300AT2-UL, RAV-SP360AT2-UL, RAV-SP420AT2-UL>