– 70 –

Reset the power supply

and then perform test run

matching to the season.

Open valve fully.

Check outdoor fan.

Defect

Replace, retightening

Replace

sensor.

Check indoor P.C. board.

Defect

Replace

Repair defective position.

Is valve fully opened?

Is there no crack or

loosening of outdoor fan?

Does not the outdoor fan

perform abnormal operation?

Does indoor fan

normally operate?

Are indoor fan motor

and connector normal?

Is there no problem

on outdoor TL sensor?

(Measurement of resistance value)

Are resistance values

of indoor TC and TCJ

sensors normal?

Replace sensor.

Check the same items as

[P22] error.

Check overcharge of refrigerant, clogging of cycle,
broken pipe, abnormal overload, etc.
Defect

Correct defective position.

Check overcharge of refrigerant, clogging of cycle,
broken pipe, abnormal overload, etc.
Defect

Correct defective position.

Eliminate interfering element.

Eliminate interfering element.

Heating season
Heating operation

Cooling season
Cooling operation

Is there no element

which interfere heat exchange

of outdoor unit?

• Clogging of heat exchanger
• Short circuit

Is there no element which

interfere heat exchange of indoor unit?

• Clogging of filter
• Clogging of heat exchanger
• Short circuit

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

YES

NO

NO

NO

NO

NO

NO

NO

CODE

No.

[P20]

Outdoor

LED display

<Display 1> <Display 2>

¡

l

¡

l

¡

¥

l

l

¡

¥

¡

¡

Check and troubleshooting

(Item without special mention Indicates part of outdoor unit.)

[High pressure protective operation]