Check outdoor P.C. board.

Defect

replace

Replace coil of 4-way valve.

Temperature sensor check

TE sensor CN601
TS sensor CN600

Indoor TC sensor

Defect

Correct and repair

Is the coil

resistance value of 4-way valve

between 1.3 and 1.6k

Ω

?

Check operation of

outdoor P.C. board.

(See below.)

Is operation of

4-way valve normal?

(Check pipe temp., etc. in

cooling/heating operation.)

Check 4-way valve.

Defect

Replace

YES

YES

NO

NO

Error

OK

CODE

No.

[P19]

Outdoor

LED display

<Display 1> <Display 2>

¡

¥

¡

¥

¡

l

l

l

¡

¥

¡

¡

Check and troubleshooting

(Item without special mention Indicates part of outdoor unit.)

[4-way valve inverse error]

Check method of outdoor P.C. board operation (Self-hold valve type)
1) Set SW804 of Dip switch as the following figure and then push SW801 for

approx. 1 second to check exchange operation to cooling cycle/heating cycle.

• Power is turned on for approx. 10 seconds.
• When checking again, check operation 1 minute or more after the first check

because exothermic of part (Coil, resistance R700) is large.

(There is no problem when coil is not connected.)

2) After check, turn off all the Dip switch SW804.

Exchange to cooling cycle

Exchange to heating cycle

Note) Check by tester

Analog tester : Good if over DC200V
Digital tester : Good if Max. value is over DC200V though the varied

value may be displayed.