Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 51

Advertising
background image

– 51 –

¡

: Go on,

¥

: Flash,

l

: Go off

ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED

Remote

controller

indication

F01
F02
F10
F29
P01
P10
P12
P31

Sensor lamp part

Block indication

Operation Timer Ready Flash

¥

¥

l

ALT

¥

¥

l

ALT

¥

¥

l

ALT

¥

¥

l

SIM

l

¥

¥

ALT

l

¥

¥

ALT

l

¥

¥

ALT

¥

l

¥

ALT

Representative defective position

Indoor unit Heat exchanger sensor (TCJ) error
Indoor unit Heat exchanger sensor (TC) error
Indoor unit Room temp. sensor (TA) error
Indoor unit Other indoor P.C. board error
Indoor unit Indoor fan error
Indoor unit Overflow detection
Indoor unit Indoor fan error
Other indoor unit error

Detection

Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor

Explanation of error contents

Open/Short of heat exchanger (TCJ) was detected.
Open/Short of heat exchanger (TC) was detected.
Open/Short of room temp. (TA) was detected.
EEPROM error (Other error may be detected. If no error, automatic address is repeated.
Indoor AC fan error was detected. (Fan thermal relay worked.)
Float switch worked.
Indoor fan error (Over-current / Lock, etc.) was detected.
Other indoor under condition of warning in group. E03/L07/L03/L08 warning

Automatic

Operation

reset

continuation

¡

Ч

¡

Ч

¡

Ч

Ч

Ч

Ч

Ч

Ч

Ч

Ч

Ч

¡

Ч

Advertising