Is flow of refrigerant by

PMV under correct conditions?

Is coil of 4-way valve

electrified during heating mode?

Does 4-way valve work correctly?

(Check pipe temperature, etc.

during cooling/heating operation.)

Check temperature sensors.

TE sensor CN600, TS sensor CN603

Indoor TC sensor

Defective

Correct or replace

Check outdoor P.C. board.

Defect

Replace

Check 4-way valve.

Defect

Replace

Check PMV.

Defect

Replace

YES

NO

NO

YES

YES

NO

Is connection of connector

CN300 correct?

Correct connection of connector.

Fan motor

exchange

Check outdoor P.C. board.

Defective

Replace

YES

YES

NO

NO

After pulling out the connector

of the fan motor CN300, rotate its shaft by hands.

Can it rotate smoothly?

Is the fan motor coil resistance within the range described below?

Between red and white lead

: 18 to 30

Ω

Between white and black lead : 18 to 30

Ω

Between black and red lead

: 18 to 30

Ω

Is AC mains voltage correct?

208/230V ± 10V

After disconnection of the compressor leads from

P.C. board, the air conditioner operates in heating mode.

Does the fan motor run?

Is there any problem on connection

of compressor lead or reactor?

(Check connection referring to the wiring diagram.)

Replace

outdoor P.C. board.

Check compressor. (Rare short, etc.)

Defective

Replace

Correct power line.

Correct wiring.

YES

NO

YES

NO

YES

NO

Check outdoor P.C. board.

Defective

Replace

CODE

No.

[P19]

[P22]

[P26]

[P29]

APPLICATION CONTROL KIT

LED display

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

¡

¡

¡

l

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

¥

l

l

l

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

l

¥

l

l

Check / Countermeasures

(Part without special mention indicates a part of the outdoor unit.)

[4-way reversal error]

∗ In case of RAV-SP180AT2-UL, the coil of 4-way valve is electrified during cooling cycling.

∗ In cooling operation, [P19] error may be displayed when the refrigerant pressure rises high abnormally.

In this case, remove the cause of pressure rising and then diagnose it again.

[Outdoor fan system error]

[Short-circuit of compressor driving device]

[Position detection circuit error]

LED display legend:

l

Go off,

¡

Go on,

¥

Flash (5Hz)