Correct and clear the cause.

Check wire connection

and correct it.

Correct power supply line.

Check outdoor P.C. board.

Defect

Replace

Check wire connection

and correct it.

Correct power supply line.

Is compressor normal?

Is there no refrigerant stagnation?

Does PMV normally operate?

Is it not abnormal overload?

Is power supply voltage normal?

208/230V ± 10V

Is power supply voltage normal?

208/230V ± 10V

Is wire connection normal?

Compressor lead

(Board side, Compressor side),

Reactor lead, Power supply lead

Is wire connection normal?

Compressor lead

(Board side, Compressor side),

Reactor lead, Power supply lead

Compressor lock

Replace

Check outdoor P.C. board.

Defect

Replace

Check TE, TS sensors and PMV.

Defect

Replace

Check outdoor P.C. board.

Defect

Replace

Check outdoor P.C. board.

Defect

Replace

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

NO

CODE

No.

[H01]

[H02]

[H03]

Outdoor

LED display

<Display 1> <Display 2>

l

¥

l

l

¡

l

l

l

¡

l

¡

¡

<Display 1> <Display 2>

l

l

l

¥

¡

l

l

l

¡

l

¡

¡

<Display 1> <Display 2>

l

¥

l

¥

¡

l

l

l

¡

l

¡

¡

Check and troubleshooting

(Item without special mention Indicates part of outdoor unit.)

[Compressor break down]

[Compressor lock]

[Current detection circuit error]