11. Compressor protective control <RAV-SP240AT2-UL only>

1) This control purposes to raise the operation frequency until 45Hz for 2 minutes in order to protect the

compressor (Prevention of oil accumulation in the refrigerating cycle) when the status that the operation

frequency is 45Hz or less has continued for 10 hours was calculated.
The operation frequency follows the normal indoor command after controlling.

2) Although the compressor may stop by THERMO-OFF control when the room temperature varies and

then attains the set temperature by this control, it is not abnormal.

3) During this control works, if stopping the operation by the remote controller, the operation does not

continue.

12. Auto restart

1) Object

It restarts the operation automatically after resetting the unexpected stop of power supply such as power

failure.

2) Contents

After returning from a power failure, the auto restart function reads the operation status from EEPROM

and then restarts the operation automatically according to the operation contents.

3) Setup of function exchange by wired remote

controller CODE No. (DN): 28

SET DATA

Auto restart

0000

None

0001

Provided