Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 58

Advertising
background image

– 58 –

CODE

No.

[P04]

APPLICATION CONTROL KIT

LED display

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

¡

l

l

¡

or

l

¡

l

¡

Check / Countermeasures

(Part without special mention indicates a part of the outdoor unit.)

[High-pressure SW error]
1. High-pressure SW error
2. Service valve closed.
3. Indoor/Outdoor fan error
4. Clogging of indoor/outdoor PMV
5. Loading of indoor/outdoor heat exchangers or short-circuit
6. Overcharge of refrigerant

Cooling operation

B

Heating operation

C

B

Cooling operation

C

Heating operation

Doesn’t high-pressure SW operate?

Are parts of high-pressure SW normal?

Does outdoor fan normally operate?

Does the indoor fan normally operate?

Are service valves fully opened?

Reset the power supply and perform
a test run appropriate to the season

Is the circuit wiring normal?

Open service valve fully.

Take measures

for defective position.

Check parts.

Defective

Replace

Isn’t there fan crack

or getting-out of fan?

Are connector connection,

capacitor and fans of the

fan motor normal?

Are resistance value

characteristics of the sensors

(TC, TCJ) normal?

Overcharge of refrigerant

Clogging / Pipe breakage /

Abnormal overload

Overcharge of refrigerant

Clogging / Pipe breakage /

Abnormal overload

Check P.C. board.

Defective

Replace

Check and repair wiring.

Connector connection /
Fan IPDU / Fan motor / Wiring

Is there any element to disturb

heat exchange of indoor unit?

Clogging of filter

Loading of heat exchanger

Short-circuit

Is there any element to disturb

heat exchange of outdoor unit?

Loading of heat exchanger

Short-circuit

Eliminate disturbing element.

Replace TC or TCJ sensor.

Repair defective position.

Check indoor P.C. board.

Defective

Replace

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

[P05]

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

¥

¥

l

l

or

¡

l

l

¡

[Power supply error (Voltage error)]

→ Refer to columns [H03] and [P04] and then check power supply and

voltage erro