Is connection of CN602 correct?

Is resistance value of TO sensor correct?

Correct connector.

Sensor error

Replace

Check outdoor P.C. board.

Defect

Replace

YES

NO

Is connection of CN603 correct?

Is resistance value of TS sensor correct?

Correct connector.

Sensor error

Replace

Check outdoor P.C. board.

Defect

Replace

YES

NO

Correct power supply line.

Does abnormal overload happen?

Is AC mains voltage correct?

208/230V ± 10V

Remove and

improve the cause of overload.

Check outdoor P.C. board.

Defect

Replace

Check and correct

wiring connection.

Is wiring connection correct?

Compressor lead

(P.C. board side, Compressor side)

Reactor cord, Power supply lead

NO

YES

YES

NO

NO

YES

Compressor lock

Replace

Correct power supply line.

Does PMV operate correctly?

Check outdoor P.C. board.

Defect

Replace

Is AC mains voltage correct?

208/230V ± 10V

Is there stagnation

of refrigerant?

Is compressor

under correct

conditions?

Check and

correct connection of wires.

TE, TS sensor,

Check PMV.

Defective

Replace

Is wiring connection correct?

Compressor lead

(P.C. board side, Compressor side)

Reactor cord, Power supply lead

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

CODE

No.

[F08]

[F12]

[H01]

[H02]

APPLICATION CONTROL KIT

LED display

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

l

¡

l

l

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

l

l

¡

l

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

¥

l

¥

l

D01

D02

D03

D04

(Red) (Yellow) (Yellow) (Yellow)

l

l

¥

l

Check / Countermeasures

(Part without special mention indicates a part of the outdoor unit.)

[Outside temp. sensor (TO) error]

[Suction temp. sensor (TS) error]

[Compressor breakdown]

[Compressor lock]

LED display legend:

l

Go off,

¡

Go on,

¥

Flash (5Hz)