5. SPECIFICATIONS OF ELECTRICAL PARTS

5-1. Outdoor Unit (Parts Ratings)

RAV-SP180AT2-UL

RAV-SP300AT2-UL, RAV-SP360AT2-UL, RAV-SP420AT2-UL

RAV-SP240AT2-UL

No.

1
2
3
4
5
6
7
8
9

10

11
12

13

Parts name

Fan motor
Compressor
Reactor
Outdoor temp. sensor (To sensor)
Heat exchanger sensor (Te sensor)
Suction temp. sensor (Ts sensor)
Discharge temp. sensor (Td sensor)
Fuse (Switching power (Protect))
Fuse (Inverter, input (Current protect))
4-way valve solenoid coil

Compressor thermo. (Protection)
Coil (Pulse Motor Valve)

Pressure switch

Type

ICF-140-43-4R

DA150A1F-21F

CH-57






STF-01AJ502E1

US-622

CAM-MD12TF-12

ACB-4UB82W

Specifications

Output (Rated) 43 W
3 phase, 4P, 1100 W
10mH, 16A
10 kΩ at 77°F (25°C)
10 kΩ at 77°F (25°C)
10 kΩ at 77°F (25°C)
50 kΩ at 77°F (25°C)
T3.15 A, AC 250 V
AC 240 V, 25 A

OFF : 257 ± 39.2°F (125 ± 4°C),

ON : 194 ± 41°F (90 ± 5°C)

OFF : 601.8 + 0

601.8

– 29 psi ⎛4.15 + 0

.2 MPa

601.8 – 29 psi

⎝4.15 – 0.2 MPa⎠

ON : 464 ± 26 psi (3.2 ± 0.2 MPa)

No.

1
2
3
4
5
6
7
8
9

10
11
12
13

14

15

Parts name

Compressor
Outdoor fan motor
Reactor
4-way valve coil
PMV coil
P.C. board
Fuse (Mounted on P.C. board)
Fuse (Mounted on P.C. board)
Fuse (Mounted on P.C. board)
Outdoor temp. sensor (TO sensor)
Heat exchanger sensor (Te sensor)
Discharge temp. sensor (Td sensor)
Heat exchanger mid. Temp sensor (TL sensor)

Compressor thermo. (Protection)

Pressure switch

Type

DA422A3F-25M
ICF-280-A100-1

CH-62

VHV-01AP552B1

UKV-A038

MCC-1571







US-622

ACB-4UB82W

Specifications

Output 100W
5.7mH, 18.5A
AC240V
DC12V
AC208 / 230 V
AC250V, 25A
AC250V, 10A
AC250V, 3.15A
10 kΩ at 77°F (25°C)
10 kΩ at 77°F (25°C)
50 kΩ at 77°F (25°C)
10 kΩ at 77°F (25°C)
OFF : 257 ± 39.2°F (125 ± 4°C),

ON : 194 ± 41°F (90 ± 5°C)
OFF : 601.8 + 0

601.8

– 29 psi ⎛4.15 + 0

.2 MPa

601.8 – 29 psi

⎝4.15 – 0.2 MPa⎠

ON : 464 ± 26 psi (3.2 ± 0.2 MPa)

No.

1
2
3
4
5
6
7
8
9

10
11
12
13

14

15

Parts name

Compressor
Outdoor fan motor
Reactor
4-way valve coil
PMV coil
P.C. board
Fuse (Mounted on P.C. board)
Fuse (Mounted on P.C. board)
Fuse (Mounted on P.C. board)
Outdoor temp. sensor (TO sensor)
Heat exchanger sensor (Te sensor)
Discharge temp. sensor (Td sensor)
Heat exchanger Temp sensor (Ts sensor)

Compressor thermo. (Protection)

Pressure switch

Type

DA220A2F-22L

ICF-280-A60-1

CH-56

VHV-01AP552B1

CAM-MD12TF-15

MCC-1571







US-622

ACB-4UB82W

Specifications

Output 60 W
5.8 mH, 18.5 A
AC200 – 240 V
DC12 V
AC208 / 230 V
AC250 V, 25 A
AC250 V, 10 A
AC250 V, 3.15 A
10 kΩ at 77°F (25°C)
10 kΩ at 77°F (25°C)
50 kΩ at 77°F (25°C)
10 kΩ at 77°F (25°C)
OFF : 257 ± 39.2°F (125 ± 4°C),

ON : 194 ± 41°F (90 ± 5°C)
OFF : 601.8 + 0

601.8

– 29 psi ⎛4.15 + 0

.2 MPa

601.8 – 29 psi

⎝4.15 – 0.2 MPa⎠

ON : 464 ± 26 psi (3.2 ± 0.2 MPa)