Toshiba CARRIER RAV-SP300AT2-UL User Manual

Page 68

Advertising
background image

– 68 –

Is there no loosening of

screws of motor drive element of

outdoor P.C. board Q200, Q300, Q400

and rectifier DB01, DB02, DB03?

Did not forget to apply

radiation grease to rear side of

Q200, DB01, DB02 or DB03?

Check outdoor P.C. board.

Defect

Replace

Remove blocking matter.

Correct short-circuit.

Open valve fully.

Correct and replace piping.

Correct connector.

Sensor error

Replace

Check outdoor P.C. board.

Defect

Replace

Correct defective position.

Replace defective part.

Repair defective position.

Recharge refrigerant.

Is there no crushed pipe?

Is valve fully opened?

Is PMV normal?

Is there no gas leak?

Is refrigerant charge amount adequate?

Check temp. sensor.

TD sensor CN603
TS sensor CN600

Is not the ventilation flue

of the heat sink blocked?

Is not the fan blocked?

(Short-circuit, etc.)

Apply radiation grease to objective part.

Retightening of screws.

(Be sure not to forget to attach insulating sheet

between heat sink and Q300, Q400.)

Error

OK

YES

YES

YES

YES

NO

NO

NO

NO

YES

YES

NO

NO

CODE

No.

[P07]

[P15]

Outdoor

LED display

<Display 1> <Display 2>

¡

¥

¡

¥

¡

¥

l

l

¡

l

¡

¡

<Display 1> <Display 2>

¡

¥

¡

¥

¡

¥

l

¥

¡

l

¡

¡

Check and troubleshooting

(Item without special mention Indicates part of outdoor unit.)

[Heat sink overheat error]

[Gas leak detection]

Advertising