8-2. Troubleshooting

8-2-1. Outline of judgment

The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with

the following method.
Method to judge the erroneous position by flashing indication on the display part of the indoor unit

(sensors of the receiving part)
The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis

are displayed restricted to the following cases if a protective circuit works.

: Go off, : Go on,

: Flash (0.5 sec.)

∗1: These are representative examples and the check code differs according to the outdoor unit to be combined.

Lamp indication

Operation Timer

Ready

No indication at all

Operation Timer

Ready

Flash

Operation Timer

Ready

Flash

Operation Timer

Ready

Alternate flash

Operation Timer

Ready

Alternate flash

Check code

E01

E02

E03

E08

E09

E10

E18

E04

P10

P12

P03

P04

P05

P07

P15

P19

P20

P22

P26

P29

P31

Cause of trouble occurrence

Power supply OFF or miswiring between receiving unit and indoor unit

Receiving error

Receiving unit

Miswiring or wire connection error

Sending error

Communication stop

between receiving unit and indoor unit

Duplicated indoor unit No.

Setup error

Duplicated master units of remote controller

Communication error between CPUs on indoor unit P.C. board

Wire connection error between indoor units, Indoor power OFF

(Communication stop between indoor header and follower)

Miswiring between indoor unit and outdoor unit or connection erorr

(Communication stop between indoor and outdoor units)

Overflow was detected.

Protective device of indoor unit worked.

Indoor DC fan error

Outdoor unit discharge temp. error

Protective device of

∗1

Outdoor high pressure system error

outdoor unit worked.

Negative phase detection error
Heat sink overheat error

Outdoor unit error

Gas leak detection error

4-way valve system error (Indoor or outdoor unit judged.)

Outdoor unit high pressure protection

Outdoor unit: Outdoor unit error

Protective device of

Outdoor unit: Inverter Idc operation

∗1

Outdoor unit: Position detection error

outdoor unit worked.

Stopped because of error of other indoor unit in a group

(Check codes of E03/L03/L07/L08)