Error mode detected by indoor unit

Check

code

E03

E04

E08

L03

L07

L08

L09

L30

P10

P12

P19

P31

F01

F02

F10

F29

E10

E18

Cause of operation

No communication from remote

controller (including wireless) and

communication adapter

The serial signal is not output from

outdoor unit to indoor unit.
• Miswiring of inter-unit wire
• Defective serial sending circuit on

outdoor P.C. board

• Defective serial receiving circuit on

indoor P.C. board

Duplicated indoor unit address

Duplicated indoor header unit

There is group wire in individual indoor

unit.

Unset indoor group address

Unset indoor capacity

Abnormal input of outside interlock

Float switch operation
• Float circuit, Disconnection,

Coming-off, Float switch contact error

Indoor DC fan error

4-way valve system error
• After heating operation has started,

indoor heat exchangers temp. is

down.

Own unit stops while warning is output

to other indoor units.

Coming-off, disconnection or short of

indoor heat exchanger temp. sensor

(TCJ)

Coming-off, disconnection or short of

indoor heat exchanger temp. sensor

(TC)

Coming-off, disconnection or short of

indoor heat exchanger temp. sensor

(TA)

Indoor EEPROM error
• EEPROM access error

Communication error between indoor

MCU
• Communication error between fan

driving MCU and main MCU

Regular communication error between

indoor header and follower units and

between main and sub units

Status of

air conditioner

Stop

(Automatic reset)

Stop

(Automatic reset)

Stop

Stop

Stop

Stop

Stop

Stop

(Automatic reset)

Stop

(Follower unit)

(Automatic reset)

Stop

(Automatic reset)

Stop

(Automatic reset)

Stop

(Automatic reset)

Stop

(Automatic reset)

Stop

(Automatic reset)

Stop

(Automatic reset)

Condition

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Displayed when

error is detected

Judgment and measures

1. Check wires of remote controller and communication adapters.

• Remote controller LCD display OFF (Disconnection)
• Central remote controller [97] check code

1. Outdoor unit does not completely operate.

• Inter-unit wire check, correction of miswiring
• Check outdoor P.C. board. Correct wiring of P.C. board.
• Check case tharmostat operation. (SP180 only)

2. When outdoor unit normally operates

Check P.C. board (Indoor receiving / Outdoor sending).

1. Check whether remote controller connection (Group/Individual)

was changed or not after power supply turned on

(Finish of group construction/Address check).
* If group construction and address are not normal when the

power has been turned on, the mode automatically shifts to

address setup mode. (Resetting of address)

1. Set indoor capacity (DN=11)

1. Check outside devices.
2. Check indoor P.C. board.

1. Trouble of drain pump
2. Clogging of drain pump
3. Check float switch.
4. Check indoor P.C. board.

1. Position detection error
2. Over-current protective circuit of indoor fan driving unit operated.
3. Indoor fan locked.
4. Check indoor P.C. board.

1. Check 4-way valve.
2. Check 2-way valve and check valve.
3. Check indoor heat exchanger (TC/TCJ).
4. Check indoor P.C. board.

1. Judge follower unit while header unit is [E03], [L03], [L07] or [L08].
2. Check indoor P.C. board.

1. Check indoor heat exchanger temp. sensor (TCJ).
2. Check indoor P.C. board.

1. Check indoor heat exchanger temp. sensor (TC).
2. Check indoor P.C. board.

1. Check indoor heat exchanger temp. sensor (TA).
2. Check indoor P.C. board.

1. Check indoor EEPROM. (including socket insertion)
2. Check indoor P.C. board.

1. Check indoor P.C. board.

1. Check remote controller wiring.
2. Check indoor power supply wiring.
3. Check indoor P.C. board.