Pnp specification, Caution – IAI America XSEL-KX User Manual

Page 40

Advertising
background image




24

Part 1 Installation

2.2. PNP Specification

(1) Input part

External Input Specifications (PNP Specification)

Item

Specification

Input voltage

24 VDC

±10%

Input current

7 mA per circuit

ON/OFF voltage

ON voltage --- 8 VDC max.
OFF voltage --- 19 VDC min.

Insulation method

Photocoupler insulation

External devices

[1] No-voltage contact (minimum load of approx. 5 VDC/1 mA)
[2] Photoelectric/proximity sensor (PNP type)
[3] Sequencer transistor output (open-collector type)
[4] Sequencer contact output (minimum load of approx. 5 VDC/1 mA)


[Input circuit]
















*

General purpose

Compact

N

I/O24V connector

0V

I/O interface pin No. 50

Caution

If a non-contact circuit is connected externally, malfunction may result from leakage
current. Use a circuit in which leakage current in a switch-off state does not exceed 1 mA.


 X-SEL controller’s input signal




At the default settings, the system recognizes the ON/OFF durations of input signals if they
are approx. 4 msec or longer. The ON/OFF duration settings can also be changed using I/O
parameter No. 20 (input filtering frequency).

Int

e

rnal

ci

rcu

it

Input terminal

External power supply

24 VDC

+10%

N*

560

3.3 K

ON duration

OFF duration

+

-

Advertising