16-11. Driving power recovery request (RPwr) and action restart request

(RAct)

(1) Driving power recovery request

㽲 How to request driving power recovery

The driving power recovery can be requested with any of the following methods:

ƒ Set the I/O parameter No. 44 (input selection function 014 = driving power restart input) to

1, and input ON edge for the input port No. 14.

ƒ Select Controller (C) from the PC software menu and execute Driving Power Recovery

Request (P).

ƒ Select Ctl (controller operation) on the Mode Selection screen of the Teaching Box and

execute RPwr (driving power recovery request).

㽳 Case where driving power recovery request is required

The driving power recovery request is required only in the following case:
ƒ Where the factor behind the driving power down occurs when the I/O parameter No. 44 is

set to 1 and the driving power recovery is attempted after the factor removal

(2) Action restart request

㽲 How to request action restart

The action restart can be requested with any of the following methods:
ƒ Set the I/O parameter No. 35 to 1 (input selection function 005 = action restart signal),

and input ON edge for the input port No. 5.

ƒ Select Controller (C) from the PC software menu and execute action restart request (L).
ƒ Select Ctl (controller operation) on the Mode Selection screen of the Teaching Box and

execute RAct (action restart request).

㽳 Case where action restart request is required

The action restart request is required in any of the following cases:

ƒ Where the controller in auto run stops with the Deadman switch when the Para-Othe No.

9 is set to 2 (Deadman SW recovery type = action continuation recovery [only in auto

run]) and recovery is attempted after the stop reset (action restart)

ƒ Where the controller in auto run makes an emergency stop when the Para-Othe No. 10 is

set to 2 (emergency stop recovery type = action continuation recovery [only in auto run])

and recovery is attempted after the emergency stop reset (action restart)

ƒ Where the safety gate is OPEN in auto run when the Para-Othe No. 11 is set to 2 (safety

gate OPEN time recovery type = action continuation recovery [only in auto run]) and

recovery is attempted after safety gate CLOSE (action restart)

ƒ Where the input port No. 6 OFF level is input (action temporary stop) in auto run when

the I/O parameter No. 36 is set to 1 (input selection function 006 = action temporary stop

signal) and recovery is attempted after the input port No. 6 ON level input (action restart)

* Where (1)

㽳 overlaps (2) 㽳, it is required to execute the driving power recovery request first and

then the action restart request.