164

7

. Absolute Reset Procedure for the Absolute Battery Unit (Option)


The absolute reset is available for the absolute battery unit using SEP-PT.

(1) Connect SEP-PT to the controller and supply main power (24V DC).
(2) “ABS Error 2” is displayed when the window is transferred to “Monitor”, “Jog”, “Inching” or

“Operation Test” window immediately after SEP-PT is started up.
Touch RES to reset the alarm.










(3) Performing the home return operation completes the absolute reset.


(Example) Home Return Operation Procedure using the “Jog” window.

Touch Pos Edit in the SEP-PT MENU window.






In the case that the password is set to the value except for “0000” before the window is
transferred to the Position Setting window, the Password Entry window appears.


Enter the value as the password using the ten-key and
touch .







When the correct password is entered, the window is transferred to the “List” window in the
Position Setting window.

Touch the position to be set.

When MENU is touched, the SEP-PT MENU window is
returned.

The left window shows the example of the Operation
Pattern 3.
The set values for each position are displayed.




The password can
be entered in the “Position Data Edit Password” in
the “Parameter Edit”

indo