Cable used, Connecting the cable, W title> warning – Yokogawa DR240 User Manual

Page 22

Advertising
background image

3-3

IM DR231-11E

Overview and Specifications of RS-422-A/RS-485 Interface

3

3.3

RS-422-A/RS-485 Interface Connection

The following explains how the RS-422-A/RS-485 module is connected to the computer.

Cable Used

There are two types of cables: two-wire cable and four-wire cable. Make sure each type meets the
following conditions.
Cable used

: twisted pair shielded cable

2 pairs of 24 AWG minimum (two-wire), 3 pairs 24 AWG mini-
mum (four-wire)

Characteristic impedance

: 100 ohm

Capacitance

: 50 pF/m

Length of cable

: 1.2 km maximum *

* Communication distance of the RS-422-A/RS-485 interface is not the linear distance, but the

total length of the cable (shielded twisted pair cable).

Terminal Arrangement of the RS-422-A/RS-485 Module

RD A Receive data A ( - )

RD B Receive data B ( + )

FG

Frame ground

SD A Send data A ( - )

SD B Send data B ( + )

SG

Signal ground

Screws used for the terminals:
ISO M4 screws, length 6 mm

Connecting the Cable

Attach crimp-on lugs (for 4 mm screws) with insulation sleeves on the leadwire ends as shown in the
diagram below. Make the exposed portion of the shielded cable to be less than 5 cm.

SD/RD A

SD/RD B

SG

FG

Shield potential

For two-wire system

For four-wire system

SD A

FG

SD B

RD B

RD A

SG

Shield

potential

Short the terminals.

<07. W Title>

WARNING

To prevent an electric shock, ensure the main power supply is turned OFF.

Note

• As shown on the next page, connect terminal RD to SD(TD) of the computer (converter) and terminal SD to RD of the

computer.