Connecting to the Host Computer

Can be connected to a host computer with RS-232-C, RS-422-A, RS-485 ports.
• In the case of RS-232-C, a converter is used as shown in the diagram below.
• For information on recommended converters, refer to “Converters” in the latter.
• Dip switch needs to be changed depending on whether it is a two-wire system or four-wire sys-

tem. Refer to “3.5 RS-422-A/RS-485 Interface Parameter Setting Procedure.”

In the case of four-wire system

In general, the recorder is wired to the host computer using a four-wire system. When four-wire
system is used, the send and receive wires need to be crossed.

Terminator (externally applied) 120 ohm, more than 1/2 W

#1

No terminators are inserted between #1 through #n-1 (internal OFF)

RS-422-A/RS-485

module

of the DA100/DR

#2

#n
(#n

31)

Terminator (Internal ON)

Host

Computer

SG

RDB( + )

RDA( - )

SDB( + )

SDA( - )

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

(Diagram below shows the case when the port of the host computer is RS-232-C)

Terminator (externally applied) 120 ohm, more than 1/2 W

#1

No terminators are inserted between #1 through #n-1 (internal OFF)

RS-422-A/RS-485

module

of the DA100/DR

#2

#n
(#n

31)

Terminator (Internal ON)

SHIELD

RD( + )

RD( - )

TD( + )

TD( - )

FG

SG

RD B

RD A

SD B

SD A

Host

Computer

Converter

Z - 101HE

(SHARP)

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

RS-232-C

3.3 RS-422-A/RS-485 Interface Connection