Sb sets whether interpolation is performed or not, Pt turns on or off every channel of trend record – Yokogawa DR240 User Manual

Page 62

Advertising
background image

6-8

IM DR231-11E

Example

Print the range list and alarm list but do not print the
parameter list related to printing or the other
parameter list.

SFON, ON, OFF, OFF

SB

Sets whether interpolation is
performed or not.

Mode

Operation mode

Setting

SBp1, p2<terminator>

p1

Channel number (001 to 560)
Computation channel number (A01 to A60)

p2

ON/OFF

Example

Perform step interpolation for channel 6 in slot 3 of
subunit 4.

SB436, ON

Comments

• If step interpolation is performed, the space

between recorded points is recorded .

• If two or more channels are step-interpolated in

the same position, the recording priority depends
on the recording color, and recording is done in
the following order:
Black > blue-purple > magenta > navy blue > red
> blue > brown > green > orange > yellow-green
For example, if two channels being recorded in
black and in blue are step-interpolated in the same
position, the overlapped parts are recorded in
black.

• The optional computation channel number for a

stand-alone model is A01 to A30.

PT

Turns on or off every channel of trend
record.

Mode

Operation mode

Setting

PTp1, p2<terminator>

p1

Channel number (001 to 560)
Computation channel number (A01 to A60)

p2

ON/OFF

Example

Turn on the analog recording of channel 6 in slot 3 of
subunit 4.

pT436, ON

Comments

• The optional computation channel number for a

stand-alone model is A01 to A30.

PD

Turns on or off every channel of
digital records.

Mode

Operation mode

Setting

PDp1, p2, p3<terminator>

p1

Channel number (001 to 560)
Computation channel number (A01 to A60)

p2

ON

Records.

OFF

Does not record.

p3

1 to 6

timer number (recording interval:

Effective only when digital records are set
for “multiple”)

Example

Perform digital recording of channel 6 in slot 3 of
subunit 4 at the interval of timer 2.

pD436, ON, 2

Comments

• The optional computation channel number for a

stand-alone model is A01 to A30.

PM

Turns on or off every channel of
manual printing.

Mode

Operation mode

Setting

PMp1, p2<terminator>

p1

Channel number (001 to 560)
Computation channel number (A01 to A60)

p2

ON/OFF

Example

Perform manual printing for channel 6 in slot 3 of
subunit 4.

PM436, ON

Comments

• The optional computation channel number for a

stand-alone model is A01 to A30.

PA

Turns on or off the alarm printing for
every channel level.

Mode

Operation mode

Setting

PAp1, p2, p3, p4<terminator>

p1

Channel number (001 to 560)
Computation channel number (A01 to A60)

p2

Level (1 to 4)

p3

OFF

No alarm printing

ON1

Printing when an alarm is generated

ON2

Printing when an alarm is generated

or reset

p4

Selection of additional message
OFF

Does not print an additional message.

01 to 20

Message number

Example

When an alarm of level 2 of channel 6 in slot 3 of
subunit 4 is generated, print the alarm and message
No. 5.

PA436, 2, ON1, 05

Comments

• When an alarm is generated or reset, the alarm

generation time or alarm type is printed.

• If an additional message is specified, the message

set with the SG command is also printed.

• The optional computation channel number for a

stand-alone model is A01 to A30.

PC

Turns on or off scale printing for
every channel.

Mode

Operation mode

Setting

PCp1, p2<terminator>

p1

Channel number (001 to 560)
Computation channel number (A01 to A60)

p2

OFF

No scale printing

ON1

Printing for every 20% of the scale

length

ON2

Printing at 0% and 100% of the scale

length

ON3

Printing at 0%, 50%, and 100% of

the scale length

Example

Print the scale of channel 6 in slot 3 of subunit 4 at
positions 0%, 50% and 100%.

PC436, ON3

Comments

• For a channel for which recording is done in

partially expanded recording, the following
applies regardless of the p2 setting:
If the recording width is 100 mm or more, printing
is carried out at positions 0%, 100% and at a point
on the partially expanded recording boundary.
If the recording width is less than 100 mm but 50
mm or more, printing is carried out at positions
0% and 100%.
If the recording width is less than 50 mm, printing
is not carried out.

• This is effective for analog recording channels.
• A channel whose recording width is less than 50

mm is not printed.

• If ON1 is set to a channel whose recording width

is less than 150 mm, the setting is invalid. Printing
is carried out at positions 0%, 50% and 100%
only.

6.4 Setting the Recording