Sw set the summer-winter time, Xk sets the key lock – Yokogawa DR240 User Manual

Page 67

Advertising
background image

6-13

IM DR231-11E

Commands

6

Example

Do not create hourly reports and create daily and
monthly reports in standard format. Create the
monthly report at 10 O'clock on the first day of every
month and the daily report at 10 O'clock everyday.

ROOFF, ON1, ON1, 01 10

Comments

• Effective only on instruments with the optional

report function.

• The report is output using TS4+device trigger

(GET)+RF.

• Date is set between 01 and 28 and hour is set

between 00 and 23 for p4.

RM

Setting report channel to ON/OFF and
the report computation type

Mode

Setup mode

Setting

RMp1, p2, p3, p4, p5<terminator>

p1

Report channel number (R01 to R60)

p2

Set the report channel to ON/OFF.

p3

Corresponding channel number
Measurement channel: 001 to 060 for stand-
alone type, 001 to 560 for extended type
Computation channel: A01 to A30 for stand-
alone type, A01 to A60 for extended type

p4

The type of computation

INST

Instantaneous value at the time when
the report is created.

AVE

Average value

SUM

Summed value

p5

Conversion of the standard unit of
time

INTVL No conversion
/sec

Convert as the summed value of the
physical amount every second

/min

Convert as the summed value of the
physical amount every minute

/hour

Convert as the summed value of the
physical amount every hour

/day

Convert as the summed value of the
physical amount everyday

Example

Set the summed value of the measurement channel
005 which is measuring the amount of flow in units
of l/min to the report channel, R02.

RMR02, ON, 005, SUM, /min

Comments

• Effective only on instruments with the optional

report function.

• If average value (AVE) is set on p4, minimum and

maximum values are also computed along with the
average value.

• If SUM is set on p4, the following computations

are carried out along with the summed value from
the time when the report was created to the next
report.
For hourly report: Total of the summed values up
to the time the daily report is created.
For daily report: Total of the summed values up to
the time the monthly report is created
Only summed value for monthly report

• The settings p3, p4 and p5 are effective when p2 is

ON.

• The setting p5 is effective only when p4 is set to

SUM.

• Since the sum is computed every measurement

interval using the sampled data, there are cases
when the physical amount per unit amount of time
is measured, the computed result differs from the
actual summed value (the measurement interval
and the unit time are different). In this case, set
the same unit used for the unit time of the physical
amount being measured to p5. The summed
values are computed using the following

converting equations depending on the
parameters.
INTVL

(measured values)

/sec

(measured values)

x

measurement

interval

/min

(measured values)

x

measurement

interval/60

/hour

(measured values)

x

measurement

interval/3600

/day

(measured values)

x

measurement

interval/86400

The unit of the measurement interval is seconds.

RI

Setting the automatic print at the time
when the report is created to ON/OFF

Mode

Setup mode

Setting

RIp1<terminator>

p1

ON

Print the report automatically at the
time when the report is created.

OFF

Do not print the report at the time
when the report is created.

Example

Print the report at the time when the report is created.
RION

Comments

• This command is effective only with optional

report function.

• If a report is being printed from the FUNC menu

of the main unit or from the RP command,
automatic printing does not take place at the time
when the report is created..

SW

Set the summer-winter time

Mode

Operation mode

Setting

SWp1,p2<terminator>

p1

Summer time or Winter time
SUMMER

Summer time

WINTER

Winter time

p2

Changing time

Example

Change to summer time at 12clock 15th June 1996

SWSUMMER,96/06/15 12

XK

Sets the key lock.

Mode

Setup mode

Setting

XKp1, p2, p3, p4, p5, p6, p7, p8<terminator>

p1

USE

Uses the key lock.

NOT

Does not use the key lock.

p2

RECORD key (LOCK, FREE)

p3

FEED key (LOCK, FREE)

p4

PRINT key (LOCK, FREE)

p5

FUNC key (LOCK, FREE)

p6

P.FUNC1 key (LOCK, FREE)

p7

P.FUNC2 key (LOCK, FREE)

p8

Pass number (0 to 9999)

Example

Lock the RECORD, FEED, PRINT keys and set the
password number to 123.

XKUSE, LOCK, LOCK, LOCK, FREE, FREE,
FREE, 123

XF

Sets the function to be displayed on
the function screen.

Mode

Setup mode

Setting

XFp1, p2<terminator>

p1

Content to be displayed on the function
screen.
ALARM_ACK
Acknowledgment of current alarm status
ALARM_RESET
Alarm is reset.
TIMER_RESET
Timer is reset.

6.5 Other Settings

Advertising
This manual is related to the following products: