6-1

IM DR231-11E

Commands

6

6.1 Setting the Input

SR

Sets the range.

Mode

Operation mode

Setting the range to SKIP

Setting

SRp1, p2<terminator>

p1

Channel number (001 to 560)

p2

SKIP

Example

Skip channel 01 of subunit 0.

SR001, SKIP

Skip channels 01 to 60 of subunit 0.

SR001-60, SKIP

Comments

• Channel(s) set to SKIP are not measured.

Setting voltage, thermocouple, RTD, contact or mA
input

Setting

SRp1, p2, p3<terminator>

p1

Channel number (001 to 560)

p2

Type of input
VOLT DC voltage
TC

Thermocouple

RTD

Resistance temperature detector

DI

Contact

mA

DC current(DR232/DR242)

p3

Measurement range

p4

Span left value

p5

Span right value

Example

Set channel 01 of subunit 1 to the thermocouple type
R,and set span left value to 0

°

C, span right value to

1760.0

°

C.

SR101, TC, R, 0, 17600

Comments

• For the p3 measurement range, see the range

parameter table on Pages 5-7 and 5-8.

• Set the span in p4 and p5 within the setting range

shown on pages 5-7 and 5-8.

• For p4 and p5 setting value, enter them within 6

digits excluding the decimal point. The decimal
point is fixed. Refer to setting range on pages 5-7
and 5-8.

• The measurement range cannot be changed while

executing a report or computation, or when a file
is written.

Setting DELTA(difference between channels)/
RRJC(remote RJC)

Setting

SRp1, p2, p3<terminator>

p1

Channel number (001 to 560)

p2

DELTA/RRJC

p3

Reference channel (01 to 60)

p4

Span left value

p5

Span right value

Example

Set channel 10 of subunit 2 to DELTA that is
difference value from channel 01 of the same
unit,and set span left value to -100.0, span right value
to 100.0.

SR210, DELTA, 01, -1000, 1000

Comments

• As the reference channel, set a channel of the

same unit as the channel to be set to DELTA or
RRJC. In addition, the reference channel number
must be smaller than the source channel number.

• For RRJC, input for the reference channel must be

of a thermocouple type.

• If the input mode (type of input, scaling...) or the

measurement range of the reference channel is
changed, DELTA or RRJC setting is cleared. The
input mode changes to the mode before the
reference channel was changed.

• If any change has been made to the number, input

mode (type of input or scaling), or measuring
range of a given reference channel, the alarm
setting of the channel for which the item
“DELTA/RRJC” is being set changes to “OFF.”

• If any change has been made to the number or

input mode (type of input or scaling) of a given
reference channel, to the measuring range, or to
the span of the set channel, the partial-expansion
setting of the channel for which the item
“DELTA/RRJC” is being set changes to “OFF.”

• Set the span in p4 and p5 within the setting range

for the reference channel shown on pages 5-7 and
5-8.

• For p4 and p5 setting value, enter them within 6

digits excluding the decimal point. The decimal
point is fixed. Refer to setting range on pages 5-7
and 5-8.

• RRJC setup is valid only for recorders with the

optional computing function.

• The measurement range cannot be changed while

executing a report or computation, or when a file
is written.

Setting the power monitor

Setting

SRp1, p2, p3, p4, p5, p6, p7<terminator>

p1

Channel number(001 to 560)

p2

AC

p3

Wiring method
1Ph2W:

Single-phase two-wire system

1Ph3W:

Single-phase three-wire system
(only on a three-wire system)

3Ph3W-2I: Three-phase three-wire system

(only on a two-voltage two-
current three-wire system)

3Ph3W-3I: Three-phase three-wire system

(only on a three-voltage three-
current three-wire system)

3Ph4W:

Three-phase four-wire system
(only on a three-wire system)

p4

Input range
25 V - 0.5 A
25 V - 5 A
250 V - 0.5 A
250 V - 5 A

p5

Measurement item

p6

Left value of span

p7

Right value of span

Example

Set subunit 1 and channel 01 to single-phase two-
wire system, input range to 25 V - 0.5 A,
measurement item to P1, left value of span to 0, and
right value of span to 100.

SR101, AC, 1Ph2W, 25V-0.5A, P1, 0, 100

Comments

• Settings of p3 and p4 are common within one

power monitor module. If the setting is changed,
the settings on other channels also change.

• For the measurement item p5, refer to the list of

measurement items on page 5-9 and 5-10.

• If the measurement item p5 is set on channels 1, 3

and 5, channels 2, 4 and 6 are set automatically
and cannot be changed. If channels 1, 3 and 5 are
set to SKIP, then channels 2, 4 and 6 can be set.

• There is a limit on what can be set on the

measurement item p5 depending on the wiring
method and the settings on other channels. If a
value outside the limit is set, settings on other
channels may change automatically. Set the
settings on each channel within the group
indicated on page 5-10.