Yokogawa DR240 User Manual

Page 65

Advertising
background image

6-11

IM DR231-11E

Commands

6

DIGITAL_PR

Digital print

GR_TREND

Trend recording in groups

MEMRY

Store measured/computed
data on a RAM disk or
write them to DR.

FLOPY

Store setup data on a
floppy disk or write them
to DR.

MATH

Computation start/stop/
reset/clear/group reset

REPORT

Report start/stop

FLAG

Set flag to 1

p5

Auxiliary action information (for p3=EDGE)
• For p4=RECORD, selection of record start

or stop (ON, OFF)

• For p4=MSG_PR or MSG_DISP, message

number (01 to 20)

• For p4=GR_TREND, group number (G01

to G07)

• For p4=MEMRY

DATA_WR When the data retention

period is LOGIC, measured/
computed data are stored at
every measurement for each
event action.

WR_TRG

Measured/computed data are
stored.

RD_TRG

Measured/computed data are
read.

LD_TRG1

Setting data are read.

LD_TRG2

Setting data are read.

LD_TRG3

Setting data are read.

• For p4=FLOPY

LD_TRG1

Setting data are read.

LD_TRG2

Setting data are read.

LD_TRG3

Setting data are read.

• For p4=MATH

START

Computation starts.

STOP

Computation stops.

RESET

Computed data are reset.

CLEAR

Computed data are cleared.

RST_G01 to RST_G07:

Computed data in the
specified group are cleared.

• For p4=REPORT

START

Report starts.

STOP

Report stops.

• For p4=FLAG

F01 to F16: Specified flag number is set to

1.

p5

Auxiliary action information (for p3=LEVL)
• For p4=MEMRY

PAUSE

Stops or restarts writing of
measured/computed data.

• For p4=FLAG

F01 to F16: Specified flag number is set to

1.

Event function setting by a remote, relay, timer,
manual function key or match time event

Setting

SLp1, p2, p3, p4, p5, p6<terminator>

p1

Event action box number (01 to 30)

p2

Event (REMOTE, RELAY, TIMER,
MFUNC_KEY, MATCH_TIME)

p3

Auxiliary action information
• For p2=REMOTE, contact number (1 to 12)
• For p2=RELAY, relay number
• For p2=TIMER, timer number (1 to 6)
• For p2=MFUNC_KEY, MFUNC_KEY

number (1 or 2)

• For p2=MATCH_TIME, match time

number (1 to 3)

p4

Action mode (EDGE, LEVL)

p5

Action
ALARM_ACK Acknowledgement of alarm

status.

ALARM_RST

Alarm reset

TIMER_RST

Timer reset

RECORD

Record start/stop

SPEED_CHG

Change to second chart
speed

MSG_PR

Message print

MANUAL_PR

Manual print

MSG_DISP

Display message

DIGITAL_PR

Digital print

GR_TREND

Trend recording in groups

MEMRY

Store measured/computed
data on a RAM disk or
write them to DR.

FLOPY

Store setup data on a
floppy disk or write them
to DR.

MATH

Computation start/stop/
reset/clear/group reset

REPORT

Report start/stop

FLAG

Set flag to 1

p6

Auxiliary action information (for p4=EDGE)
• For p5=RECORD, record start/stop

selection (ON, OFF)

• For p5=MSG_PR, MSG_DISP, message

number (01 to 20)

• For p5=GR_TREND, group number (G01

to G07)

• For p5=MEMRY

DATA_WR When the data retention

period is LOGIC, measured/
computed data are stored at
every measurement for each
event action.

WR_TRG

Measured/computed data are
stored.

RD_TRG

Measured/computed data are
read.

LD_TRG1

Setting data are read.

LD_TRG2

Setting data are read.

LD_TRG3

Setting data are read.

• For p5=FLOPY

LD_TRG1 Setting data are read.
LD_TRG2 Setting data are read.
LD_TRG3 Setting data are read.

• For p5=MATH

START

Computation starts.

STOP

Computation stops.

RESET

Computed data are reset.

CLEAR

Computed data are cleared.

RST_G01 to RST_G07:

Computed data in the
specified group are cleared.

• For p5=REPORT

START

Report starts.

STOP

Report stops.

• For p5=FLAG

F01 to F06: Specified flag number is set to

1.

p6

Auxiliary action information (for p4=LEVEL)
• For p5=GR_TREND, group number (G01

to G07)

• For p5=FLAG

F01 to F16: Specified flag number is set to

1.

Example

Set an event action to record message number 04
when the chart ends in event action box 02.

SL02, CHART_END, EDGE, MSG_PR, 04

Comments

• With an action as the start (event), another action

(action) can be executed automatically.

• Thirty types of event actions can be set.
• If the action mode is EDGE, the set action

continues even if the event action is over.

6.5 Other Settings