Yokogawa DR240 User Manual

Page 52

Advertising
background image

5-9

IM DR231-11E

Command Format

5

Pulse Input

Nominal

Parameter input format

Setting range

RATE

RATE

0 to 30000

GATE

GATE

0 to 30000

Measuring Items of Power Monitor

Vi (i=1, 2, 3); Root mean square voltage
V13 = (V1+V3)/2
V0 = (V1+V2+V3)/3
Ii (i=1, 2, 3); Root mean square current
I13 = (I1+I3)/2
I0 = (I1+I2+I3)/3
Pi (i=1, 2, 3); Active power
P13 = P1+P3
P0 = P1+P2+P3
Vari (i=1, 2, 3); Reactive power
Var13 = Var1+Var3
Var0 = Var1+Var2+Var3
VAi (i=1, 2, 3); Apparent power
VA13 = VA1+VA3
VA0 = VA1+VA2+VA3
PFi (i=1, 2, 3); Power factor
PF13 = P13/(P13

2

+Var13

2

)

1/2

=P13/VA13

PF0 = P0/(P0

2

+Var0

2

)

1/2

=P0/VA0

PHi (i=1, 2, 3); Phase angle
PH13 = tan

-1

(Var13/P13)

PH0 = tan

-1

(Var0/P0)

FREQ; Frequency

5.5 Input Range Parameter

Advertising