3 setting a channel no., and alarm output relay no – Yokogawa DR240 User Manual

Page 47

Advertising
background image

5-4

IM DR231-11E

5.3

Setting a Channel No., and Alarm Output Relay
No.

Channel and relay numbers are expressed as shown below in three characters.
Unit No. + Slot No. + Number in slot

1

2 3

Channel/relay No.

Slot No. (In case of channel/relay No. 10, Slot No. + 1)

Unit No. ("A" for optional computation channel)

Channel Number

DR130/DR231/DR241 (Stand-alone type)

DR232/DR242 (Expandable type)

Unit No.

0

0 to 5 (Subunit: DS400/DS600)

Slot No.

0 to2 (0 or 1 for DR130)

0 to 5

Channel No.

1 to 10 (CH10: 0)*

1 to 10 (CH10: 0)*

*:

For CH10, the channel number digit is expressed by 0 and the slot number digit, by slot number + 1.

Note

• If successive channel numbers are to be specified, enter as ABC-DE, where

ABC: the above 3-digit channel number (unit no., slot no., and channel no.)

DE: the channel number except the unit number (slot no., and channel no.)

Successive channels can only be specified for a unit.

• The input module cannot be mounted to the DR232/DR242 main unit.

Relay Number

DR130/DR231/DR241 (Stand-alone type)

DR232/DR242 (Expandable type)

Unit No.

0

I (DR232/DR242 main unit)*

1

S(Internal switch)

S(Internal switch)
0 to 5 (Subunit: DS400/DS600)

Slot No.

1 to 5 (1 to 3 for DR130)

0 to 5

Relay No.

1 to 10 (Relay No. 10: 0)*

2

1 to 10 (Relay No. 10: 0)*

2

*1: If the recorder comprises any communication module, no alarm-output relay module can be mounted on

the recorder’s main unit. The unit number “I,” therefore, is not usable in setting up the recorder using
communication commands.

*2: For relay No. 10, the channel number digit is expressed by 0 and the slot number digit, by slot number + 1.

Example

• Channel 9 of the module mounted in slot 2 of the unit 3 of the extended model: 329
• Relay of No. 10 of the module mounted in slot 2 of the unit I of the extended model: I30

1

3

5

7

9

2

4

6

8

10

2

4

6

8

10

1

3

5

7

9

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Stand alone model (DR231/DR241)

Module

Stand alone model (DR130)

Slot 0

Slot 1

Slot 2

Slot 3

P O W E R

1 0 0 - 2 4 0 V 5 0 / 6 0 H z 7 0 V A M A X

STATUS

SUB UNIT

P O W E R

1 0 0 - 2 4 0 V 5 0 / 6 0 H z 7 0 V A M A X

STATUS

SUB UNIT

UnitI

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Unit No.
0 to 5*

1

(Sub-unit
DS400/DS600)

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Expandable model (DR232/DR242)

Unit No.
setting switch

*1 : The unit number of the sub-unit is the number

set by the switch located on each unit below

slot 2.
Make sure the settings comform the switch
setting.