Edwards Signaling eFSA250 User Manual
Page 116
Chapter 2: Front panel programming
104
E-FSA64 and E-FSA250 Technical Reference Manual
To change the relay/sounder base type and follow option:
1. Press the Menu button, and then choose
Programming.
2. Choose Advanced Program and enter the level 2
password.
3. Choose Loop Configuration and select the loop
number. (This option is displayed only if the panel
has two loops.)
4. Choose Devices, and then enter the number of the
device to be programmed. The serial number of
the device is displayed.
5. Press the Enter button.
6. Choose Base Type and select either Relay or
Sounder.
7. Choose Follow and select one of the types listed
in Table 26 on page 95.
8. Choose Save.
9. Press the Menu button to exit menu mode, or
continue programming.
Main Menu
Test
Control
Program
Program
Incremental Program
Auto Program
Advanced Program
Enter Password
0000
Advanced Program
Loop Configuration
Panel Configuration
Panel Operation
Loop Configuration
Zone
Correlation Groups
Device
Device
Number 001
Serial # 12345687890
Device 001
Day Prealarm% Off<>
Night Prealarm Off<>
Base Type Relay<>
Programming relay modules and bases as latched
output devices
Latched outputs are relays that are configured to shut down air handlers and
dampers during an alarm. The table below lists relay modules and relay bases
that can be configured as latched outputs. The following table lists the device
types used to configure a device as a latched output.
The latched outputs must be manually unlatched and then restored. The unlatch
command affects all latched outputs system-wide. You can assign the Unlatch
Outputs command to a programmable key on the front panel or to an input
module. The following output modules can be configured to unlatch latched
outputs: E-ISO, E-IDC1A, E-IDC1B, or E-IDC2B.