Chapter 2: Front panel programming

104

E-FSA64 and E-FSA250 Technical Reference Manual

To change the relay/sounder base type and follow option:

1. Press the Menu button, and then choose

Programming.

2. Choose Advanced Program and enter the level 2

password.

3. Choose Loop Configuration and select the loop

number. (This option is displayed only if the panel

has two loops.)

4. Choose Devices, and then enter the number of the

device to be programmed. The serial number of

the device is displayed.

5. Press the Enter button.
6. Choose Base Type and select either Relay or

Sounder.

7. Choose Follow and select one of the types listed

in Table 26 on page 95.

8. Choose Save.
9. Press the Menu button to exit menu mode, or

continue programming.

Main Menu

Test

Control

Program

Program

Incremental Program

Auto Program

Advanced Program

Enter Password

0000

Advanced Program

Loop Configuration

Panel Configuration

Panel Operation

Loop Configuration

Zone

Correlation Groups

Device

Device

Number 001

Serial # 12345687890

Device 001

Day Prealarm% Off<>

Night Prealarm Off<>

Base Type Relay<>

Programming relay modules and bases as latched

output devices

Latched outputs are relays that are configured to shut down air handlers and

dampers during an alarm. The table below lists relay modules and relay bases

that can be configured as latched outputs. The following table lists the device

types used to configure a device as a latched output.
The latched outputs must be manually unlatched and then restored. The unlatch

command affects all latched outputs system-wide. You can assign the Unlatch

Outputs command to a programmable key on the front panel or to an input

module. The following output modules can be configured to unlatch latched

outputs: E-ISO, E-IDC1A, E-IDC1B, or E-IDC2B.