Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

67

3. Enter a level two password.
4. When the “Current config. will be lost screen!,”

message displays on the LCD:
Select Continue to continue with auto

programming
— or —
Select Cancel to return to the programming menu.

5. Set auto programming options.

Note:

Use the right or left arrow button rather than

the Enter button to select values for each option.

The Enter button begins the auto programming

operation no matter which option the cursor is on.

Also, the options you select are preserved and will

be displayed the next time you auto program.

6. When you have finished, press Enter.

The panel begins auto programming and displays

the number of devices on the system. If you have

more than one loop, the device counts are per

loop. If you previously programmed the panel, The

system displays the number of old and new

devices.

7. Press Enter to continue.

Auto programming continues based on the

settings you made above.

8. When prompted, program the options you selected

using the procedures that follow. For example, if

you are using a dialer, auto programming requires

you to program specific dialer options.

9. When auto programming is complete, the system

displays the banner screen.

Control

Program

Program

Incremental Program

Auto Program

Advanced Program

Enter Password

0000

Current config.

will be lost!

Continue

Cancel

Auto Program

Auto Zoning Yes>

Evnt Notif Device>

Label Devices? Yes>

Auto Program

System Busy

################

<Back <Cancel

Devices Old/New

Loop 1 XXX/YYY

Loop 2 XXX/YYY

<Continue

— or —

Devices: Old/New

XXX/YYY

<Continue