Chapter 2: Front panel programming

106

E-FSA64 and E-FSA250 Technical Reference Manual

To configure a relay module or base as a latched output:

1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2

password.

3. Choose Loop Configuration.
4. Choose Device.
5. If the panel has multiple loops, choose the loop to

be configured.

6. Enter the device address to be configured. Device

details are displayed.

7. Set the Base Type option to Relay.
8. Set the Follow option to None.
9. Set the Latched option to Yes.
10. Choose Type and select one of the Latched

Outputs types listed in Table 27 on page 105.

11. Press the Menu button to exit menu mode, or

continue programming.

Loop configuration

Zone

Correlation groups

Device <>

Device

Number 001

Serial # 5199776279

Device 005/001

Base Type Relay

Follow None

Latched Yes

Advertising