Disabling and enabling the dialer and network, Initiating a fire drill – Edwards Signaling eFSA250 User Manual
Page 188
Chapter 3: System operation
176
E-FSA64 and E-FSA250 Technical Reference Manual
Disabling and enabling the dialer and
network
Disabling the dialer, network CMS connection, or any panel or device NACs
configured as City Tie prevents transmission of events to the central monitoring
station (CMS).
When you enable the dialer and network CMS connection:
• The Remote Disconnect LED turns off
• The message “Dialer Dsbl/Rem Disc” on the LCD disappears
• The disabled points indicator on the LCD decrements
• The active points indicator on the LCD decrements
To disable or enable the dialer and network card:
1. Press Remote Disconnect.
2. Enter a level one password.
Initiating a fire drill
Pressing Drill activates all audible and visible notification appliances according to
the panel programming, but does not activate the alarm relay.
Note:
Drill does not operate when the panel has an active alarm or supervisory
event.
To start a fire drill:
1. Press the menu button and choose Control.
2. Enter a level one password.
3. Choose Drill.
The control panel turns on all notification appliance circuits.
To stop a fire drill:
1. Press the menu button and choose Control.
2. Choose Drill.
The control panel turns off all notification appliance circuits.