Appendix d applications, Local alarm signaling applications – Edwards Signaling eFSA250 User Manual

Page 271

Advertising
background image

E-FSA64 and E-FSA250 Technical Reference Manual

259

Appendix D

Applications

Summary

This appendix has sounder base applications that can be used with the SB4U

sounder base.

Content

Local alarm signaling applications 259

What is local alarm signaling? 259

Typical wiring for a local alarm signaling application 260

Programming sounder bases for a local alarm signaling application 260

Correlated zone and system alarm signaling applications 261

Zone alarm signaling applications 261

System alarm signaling applications 263

Programming for a system alarm signaling application 264

In-suite signal silence applications 265

Local alarm signaling applications

What is local alarm signaling?

In local alarm signaling applications, an audible detector base (sounder base)

automatically sounds an alarm signal when its detector is activated. All other

sounder bases on the same riser remain silent until their detectors are activated.
The sounder base continues to sound an alarm signal until smoke is cleared from

its detector and the control panel is reset.