Edwards Signaling eFSA250 User Manual

Page 168

Advertising
background image

Chapter 3: System operation

156

E-FSA64 and E-FSA250 Technical Reference Manual

ID

Event description

042 Common alarm: An alarm event is

taking place on the control panel

043 Common supervisory: A supervisory

event is taking place on the control

panel

044 Common monitor: A monitor event is

taking place on the control panel

045 Common trouble for telco dialer: A

trouble event, other than a DACT

delivery fault is taking place on the

control panel

046 Common trouble for network dialer: A

trouble event, including a DACT delivery

fault is taking place on the control panel

047 Outputs Are Latched: Outputs in the

system are in latched condition

048 Self test fault: A fault was detected

while testing the panel’s internal

subsystems (memory, flash, code, etc.)

049 Internal fault: The control panel

detected an internal hardware or

software error

050 Dialer dsbl/rem disc: The dialer was

disabled by the Remote Disconnect

button

051 Dialer line 1 fault: A ground fault or line

fault was detected on line 1 of the dialer

052 Dialer line 2 fault: A ground fault or line

fault was detected on line 2 of the dialer

ID

Event description

053 Dialer delivery fail: The dialer failed to

deliver a message to the receiver or

CMS

054 Dialer normal test: A dialer test was

conducted when the panel was in a

normal state

055 Dialer abnormal test: A dialer test was

conducted when the panel was in an

off-normal state

056 Dialer configuration: The dialer is not

programmed or has unverified changes

057 Net Comm Fault 01: Communications

between the panel and network receiver

01 failed

058 Net Comm Fault 02: Communications

between the panel and network receiver

02 failed

059 Net Comm Fault 03: Communications

between the panel and network receiver

03 failed

060 Net Comm Fault 04: Communications

between the panel and network receiver

04 failed

061 Net Comm Fault 05: Communications

between the panel and network receiver

05 failed

062 Net Comm Fault 06: Communications

between the panel and network receiver

06 failed

063 Net Comm Fault 07: Communications

between the panel and network receiver

07 failed

Advertising