Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

73

Adding and removing devices from

programmed systems

You can add an additional device or several devices to a system that has already

been programmed without reentering programming mode. Once the device is

installed, the panel signals a trouble active event and indicates on the LCD

screen that there is an unconfigured device. The device can then be

programmed and added to the database.

Notes

• If you are adding more than a few devices, you may want to use the

Incremental programming option that lets you quickly add and label the

devices. See “Performing incremental programming” on page 69.

• You must log on with a level two password to add a device.

Device programming options

Table 24 below describes the options to be set when programming devices.

Table 24: Device options
Device option Description

Zone

Select the zone you want to add this device to or select Off if you are not adding

the device to a zone.

Zone

secondary

Select the zone to which you want to add this device (secondary element), or

select Off when you are not adding the device (secondary element) to a zone.

See Table 9 on page 43.

Label

Enter a text label for the device (two lines of 20 characters). When you have

finished, select Save.

Correlation

groups

Assigns the device to one or more correlation groups. For more information, see

“What is a correlation group?” on page 32.
Enter the number of the correlation group to which the device is assigned.

Choose Included or Excluded.
• “Included” adds assigns the item to the group.
• “Excluded” removes the item from the group
When you have finished, choose Save.