Chapter 4: Reports

E-FSA64 and E-FSA250 Technical Reference Manual

191

To view a Response Quality diagnostic report:

1. Press the Menu button and choose Reports.
2. Choose Diagnostics.
3. Choose Response Quality.
4. Enter the quality percentage (0 to 100).

This is a communication percentage value that is

used to display the device’s minimum recorded

pulse strength percentage. Enter “80” to list

devices that are communicating up to 80 percent

of their maximum pulse strength. Enter “50” to list

devices that are communicating up to 50 percent

of their maximum pulse strength (devices

communicating better than 50% are not included

in the report).

Main Menu

Reports

Test

Control

Program

Reports

Internal Status

Device Details

Diagnostics

Diagnostics

Comm Retries

Response Quality

Response Quality

Quality % 000

Internal Fault report

The Internal Fault report displays information about an internal fault event (event

ID 48) that has occurred in the system. The report contains information that is

important for technical support when troubleshooting the internal fault event and

should typically only be run when you are asked to do so by a technical support

representative.

To view an Internal Fault report:

1. Press the menu button and choose Reports.
2. Choose Int. Fault.

Main Menu

Reports

Test

Control

Program

Reports

Device Details

Diagnostics

Int. Fault