Chapter 2: Front panel programming

48

E-FSA64 and E-FSA250 Technical Reference Manual

Table 17: Latched output device types [1]
Device type

Description

Continuous

nonsilenceable (latched)

For Class B latched output modules that output an unsynchronized

signal. Does not follow signal silence.

Continuous

nonsilenceable Class A

(latched)

For Class A latched output modules that output an unsynchronized

signal. Does not follow Signal Silence.

Relay nonsilence NC

(latched)

For relay devices functioning as latched output devices that open

when activated. Does not follow signal silence.

Relay nonsilence NO

(latched) latch

For relay devices functioning as latched output devices that close

when activated. Does not follow signal silence.

Relay nonsilenceable

(latched)

For Class B relay devices functioning as latched output devices.

Does not follow signal silence.

Supervised output

(latched)

For Class B latched output modules that output an unsynchronized

signal. Does not follow signal silence.

Supervised outputs Class

A (latched)

For Class A latched output modules that output an unsynchronized

signal. Does not follow Signal Silence.

[1] Table 27 on page 105 gives a full list of devices configurable as latched output devices.

Displaying the Program menu

Use the Program menu to access the options that let you program your panel.

To display the program menu:

1. Press the Menu button.
2. Choose Program.
3. Press Enter.

Setting the time and date

The first step in programming the panel is setting the time and date. You must do

this before using either the Auto Program or Advanced Program command.

To set the time and date:

1. Press the Menu button and choose Program.
2. Choose Date and Time.