Silencing panel and annunciator buzzers, Silencing notification appliances – Edwards Signaling eFSA250 User Manual

Page 173

Advertising
background image

Chapter 3: System operation

E-FSA64 and E-FSA250 Technical Reference Manual

161

• When the reset process is complete, “Reset” clears from the LCD and the

Reset LED turns off.

• If the condition causing an "Alarm Active" condition has not cleared (smoke is

still present in detector chamber, pull station was not reset, etc.) the panel

remains in an alarm state after resetting and the NACs and other outputs do

not reactivate.

• Disabled devices and zones remain disabled after the panel is reset.
• Resetting the panel does not log off user level one or user level two access.

Silencing panel and annunciator buzzers

The panel buzzer sounds whenever an event message is received at the control

panel. Pressing the Ack/Panel Silence button:
• Silences the buzzer on the control panel and all remote annunciators.

• Acknowledges all current event messages.

• Silences the panel buzzer on all remote annunciators. If more than one event

is queued, the LCD displays event 001.

To silence the buzzer:

1. Determine what event caused the buzzer to sound by pressing Enter to view

the event details. This displays the loop number, device address, and a

detailed description of the event type.

2. Press the Ack/Panel Silence button on the panel, or the Ack/Silence button on

any remote annunciator.

Silencing notification appliances

WARNING: Do not silence notification appliances until the building is fully

evacuated and the cause of the alarm has been determined.

To silence or resound notification appliances:

1. Press the Signal Silence button.