Chapter 1: Installation and wiring

8

E-FSA64 and E-FSA250 Technical Reference Manual

Figure 8: Battery wiring location

Figure 9: Battery wiring

TB8

Red

Black

12 VDC

Battery

12 VDC

Battery

+

Notification appliance circuit wiring (TB2)

The control panel provides either two or four notification appliance circuits

depending on which model you have. Each circuit can be individually configured

for continuous, temporal, synchronized, coded, or city tie output.

Circuit specifications

• Class B or Class A.
• Circuit voltage: 24 VFWR, regulated
• Circuit current

Edwards Signaling eFSA64 panel:

3.75 A total, 2.5 A max. per circuit at 120/230 VAC 60 Hz input voltage

3.0 A total, 2.5 A max. per circuit at 230 VAC 50 Hz input voltage