Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

125

AC voltage programming

AC Voltage is used to select the rated voltage of the mains supply connected to

the control panel. The possible values are 110, 115, 120, 220, 230, and 240

VAC.

Note:

Use 110, 115, and 120 only on 120 VAC control panel models. Use 220,

230, and 240 only on 230 VAC control panel models.

To set the AC voltage:

1. Display the panel configuration options menu. See

“Panel programming” on page 109.

2. Choose AC Voltage.
3. Select 110, 115, 120, 220, 230, or 240.
4. Program other panel configuration options or

choose Save if you’re finished.

5. Press the Menu button to exit menu mode, or

continue programming.

Panel Configuration

GWY 000.000.000.000

Lock Rmt Read Yes<>

AC Voltage 120<>

Panel Configuration

Lock Rmt Read Yes<>

AC Voltage 120<>

Save

Panel operation programming

The panel operation options control how the panel operates. Most options have a

factory default setting that you can accept or change. See “Factory default

settings” on page 36.

Table 35: Panel operation options
Option

Description

Language

Select the desired display language: English or French.

Marketplace

Select the desired marketplace: U.S. or Canada.

AC fail delay

Set the AC fail delay time to:
Off: Off-premises notification of an AC power failure is

immediate. The “off” setting is not acceptable for UL/ULC

installations. See “UL 864 programming requirements” on page

31 for details.
1 to 15 hours: Delays the off-premises notification of an AC

power failure by the time period selected.