Panel operation programming – Edwards Signaling eFSA250 User Manual
Page 137
Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
125
AC voltage programming
AC Voltage is used to select the rated voltage of the mains supply connected to
the control panel. The possible values are 110, 115, 120, 220, 230, and 240
VAC.
Note:
Use 110, 115, and 120 only on 120 VAC control panel models. Use 220,
230, and 240 only on 230 VAC control panel models.
To set the AC voltage:
1. Display the panel configuration options menu. See
“Panel programming” on page 109.
2. Choose AC Voltage.
3. Select 110, 115, 120, 220, 230, or 240.
4. Program other panel configuration options or
choose Save if you’re finished.
5. Press the Menu button to exit menu mode, or
continue programming.
Panel Configuration
GWY 000.000.000.000
Lock Rmt Read Yes<>
AC Voltage 120<>
Panel Configuration
Lock Rmt Read Yes<>
AC Voltage 120<>
Save
Panel operation programming
The panel operation options control how the panel operates. Most options have a
factory default setting that you can accept or change. See “Factory default
settings” on page 36.
Table 35: Panel operation options
Option
Description
Language
Select the desired display language: English or French.
Marketplace
Select the desired marketplace: U.S. or Canada.
AC fail delay
Set the AC fail delay time to:
Off: Off-premises notification of an AC power failure is
immediate. The “off” setting is not acceptable for UL/ULC
installations. See “UL 864 programming requirements” on page
31 for details.
1 to 15 hours: Delays the off-premises notification of an AC
power failure by the time period selected.