Updating the firmware – Edwards Signaling eFSA250 User Manual

Page 69

Advertising
background image

Chapter 2: Front panel programming

E-FSA64 and E-FSA250 Technical Reference Manual

57

Updating the firmware

The Firmware Update Utility (FUU) lets you install new firmware in your main

panel or expansion panels. It also lets you retrieve the current firmware version in

your panel.
The utility runs on a laptop or PC connected to a panel using a TCP/IP or

USB/Serial connection. The utility works with panels already installed with

firmware version 2.2, or higher.

To update the firmware from the front panel:

1. Press the Main Menu button and choose Program.
2. Choose Firmware Updates.
3. Enter a level two password.
4. Select Initiate to start the firmware download.
The Download Status menu displays showing the

target as “None” and status as “Waiting”.

Main Menu

Reports

Test

Control

Program

Program

RS232 CU Enable

Programmable Keys

Firmware Update

Enter Password

0000

Firware Update

Initiate

Abort

Status

Status

Target None<>

Status Waiting<>

:Continue :Back

To update the firmware from the firmware update utility:

1. After initiating the firmware update from the panel, enter the Level 2 password

in the Properties window of the FUU in order to establish communication with

panel.

2. Select a connection method (RS232 or TCIP), and then enter the

corresponding fields required to connect to the panel in properties window.

3. Select the desired target panel (main or expansion) in the Panel Select field.
4. Browse to the desired image by clicking Browse button in the Image Path

field.

Advertising