Chapter 2: Front panel programming

52

E-FSA64 and E-FSA250 Technical Reference Manual

Note:

The current language, marketplace, and loop device configuration settings

are not affected by the Restore Defaults command.

To restore the default settings:

1. Press the Menu button and choose Program.
2. Choose Restore Defaults.
3. Enter a level two password.
4. Select either Panel Only, CMS Only, or Panel and

CMS.
Panel only: Restores only the panel’s defaults

(panel operation and panel configuration options)
CMS only: Restores only the dialer, network (1-8)
Panel and CMS: Restores both the panel and

CMS device defaults

5. Press Enter.
6. Return to the Program menu.
7. Choose Panel Restart.
8. Choose Yes.

The panel restarts, and the factory default settings

are reloaded into the database.

Main Menu

Reports

Test

Control

Program

Program

Clear History

Password

Restore Defaults

Enter Password

0000

Restore Defaults

Panel Only

CMS Only

Panel and CMS

Setting up the programmable keys

There are two control panel buttons that can be assigned to correlation groups in

order to:
• Disable and reenable panel NACs, devices, and zones

• Activate panel NACs and devices

• Restore panel NACs and devices

• Unlatch all output devices globally

Notes

• You cannot disable a NULL device when it is part of a correlation group.
• You cannot configure user keys for correlation groups.