Edwards Signaling eFSA250 User Manual

Page 136

Advertising
background image

Chapter 2: Front panel programming

124

E-FSA64 and E-FSA250 Technical Reference Manual

9. Press the Menu button to exit menu mode, or

continue programming.

Port CU programming
To communicate with the CU, you must enter the same TCP/IP port number that

you defined in the CU’s TCP IP Port field.

To set the port CU:
1. Display the panel configuration options menu. See

“Panel programming” on page 109.

2. Choose Port CU.
3. Enter the TCP/IP port number (1025 to 65535)

that you entered in the Configuration Utility. The

default is 2505. (Ports 1 to 1024 are reserved.)

Panel Configuration

MSK 255.255.255.000

GWY 000.000.000.000

Port CU 02505

Setting the Lock Remote Read function

Lock remote read controls incoming TCP/IP communications when a network

card is installed and it is connected to a LAN or WAN. It restricts telnet, ping, and

CU read requests at the panel so that unwanted access to the panel is restricted,

almost like a firewall.

Note:

Lock remote read is active when no one is logged onto the panel or when

someone uses a level one password to log on. When you log with a level two

password, all communication options are available and there are no restrictions.

To set the Panel Configuration lock remote read option:

1. Display the panel configuration options menu. See

“Panel programming” on page 109.

2. Choose Lock Rmt Read.
3. Select either:

Yes: telnet, ping, and CU read access to the panel

are restricted.
No: telnet is restricted, but ping and CU read

access to the panel are allowed.

4. Program other panel configuration options or

choose Save if you’re finished.

5. Press the Menu button to exit menu mode, or

continue programming.

Panel Configuration

MSK 255.255.255.000

GWY 000.000.000.000

Lock Rmt Read Yes<>

Panel Configuration

GWY 000.000.000.000

Lock Rmt Read Yes<>

Save