Appendix A: Panel specifications

208

E-FSA64 and E-FSA250 Technical Reference Manual

Control panel specifications

eFSA64 panel

eFSA250 panel

Device loops

1 loop Class B or Class A (Styles

4, 6, 7) supporting up to 64 device

addresses (any combination of

detectors and modules)
Maximum T-taps: 63 (each device

can be on its own branch)

1 loop, expandable to 2, Class A or

B (Styles 4, 6, 7), each loop

supporting up to 127 device

addresses (any combination of

detectors and modules but not

more than 126 modules per loop)
Maximum T-taps/loop: 126

Notification appliance

circuits

2 Class B (Style Y), Class A (Style

Z) optional
3.75 A FWR total at 120/230 VAC

60 Hz
3.0 A FWR total at 230 VAC 50 Hz
2.5 A FWR each max. per circuit

4 Class B (Style Y) or 2 Class A

(Style Z)
6.0 A FWR total at 120/230 VAC

60 Hz
5.0 A FWR total at 230 VAC 50 Hz
2.5 A FWR each max. per circuit

Primary power

120 VAC, 60 Hz, 1.3 A max.
230 VAC, 50-60 Hz, 0.62 A max.

120 VAC, 60 Hz, 2.0 A max.
230 VAC, 50-60 Hz, 0.97 A max.

Base panel current

standby

155 mA

172 mA

Base panel current

alarm

204 mA

267 mA

Input zones

16 max.

32 max.

Remote annunciator

8 drops max., RS-485 Class B,

Class A is optional
Data line length: 4,000 ft.

(1,219 m)

8 drops max., RS-485 Class A or B
Data line length: 4,000 ft. (1,219 m)


Operating voltage

24 VDC

Auxiliary power output

circuit

Aux power 1: 500 mA, 24 VDC
Aux power 2: 500 mA, 24 VDC (1 A possible if you reduce total

available NAC power by 500 mA)
Output: 28.3 to 21.9 VDC, special application

Note:

For a complete list of devices that can be connected to this circuit,

see the Edwards Signaling eFSA64 and eFSA250 Series Compatibility

List (P/N 3101199).